beautypg.com

Fig. 5 — control circuit connections, Start-up, Refrigerant charging – Carrier 38EB User Manual

Page 6

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

THERMOSTAT SUBBASE
HH93AZ042 OR
HH93AZ040

38EB

I

- j

TO IFM LINE
VOLTAGE

:}“\POWER

SUPPLY

“©n

TRANS

ARRANGEMENT A-(COOLING ONLY)

THERMOSTAT SUBBASE

ARRANGEMENT B-ONE TRANSFORMER
(COOLING AND ONE-STAGE HEATING)

THERMOSTAT

SUBBASE

HH93AZI76

ARRANGEMENT C-ONE TRANSFORMER

(COOLING AND TWO-STAGE HEATING)

IFR, FS and IFM are located in furnace on heating-cooling

applications If accessory IFR is required for cooling-only
applications, locate (IFR) in fan coil

‘Connect FS to low-speed indoor fan terminal when 2-speed fan

is used

C — Contactor (12-va)

Trans — Transformer

FS — Fan Switch
HC — Heating Control

Field Splice

IFM — Indoor Fan Motor

________ Field Wiring

IFR — Indoor Fan Relay

________ Factory Wiring

NOTE Refer to unit wiring label for wire colors: C to G and C to Y
connections

>• Fig. 5 — Control Circuit Connections

START-UP

1. Backseat (open) liquid and suction line service

valves.

2. Set thermostat selector switch at OFF.

3. Set room thermostat at desired temperature.

Be sure this temperature is below indoor ambient.

4. Close electrical disconnects energizing entire

system.

5. Set room thermostat at COOL and fan switch at

FAN or AUTO, as desired. Operate unit for 15
minutes; then check system refrigerant charge.
See Refrigerant Charging, below.

Motors and controls are designed to operate satis­

factorily in the voltage range shown in Table 4. If

necessary to use manifold gages for servicing, refer
to Carrier Standard Service Techniques Manual,
Chapter 1, Refrigerants, page 1-5, Fig. 8 for bypass

method of returning charge to system. Removal of
liquid line charging hose without following these
precautions could result in some loss of charge.

Refrigerant Charging

CAUTION: To

Do sot morchsrge sysiiem. As ovorcbsf®e

cas

Condensing units contain correct operating

charge for complete system when connected to

Carrier-approved evaporators of same capacity as
condensing unit with 25 ft or less of Carrier accessory
tubing or field-supplied tubing of recommended
size. For every 10 ft of liquid line of recommended
size over 25 ft, add refrigerant charge as follows: .41b
for 3/8-in. line; .28 lb for 5/ 16-in. line. On all other
systems, adjust charge for correct operation as
applicable.

Service port connections are provided on liquid

and suction line service valves for evacuation and
charging. See Fig. 1.

TO CHECK, ADJUST OR REPLACE REFRIG­

ERANT CHARGE use method recommended in

Table 6. Details of charging methods are listed
below.

Before recharging system, thoroughly evacuate

system and then weigh in refrigerant charge speci­
fied in Table 5. Check or adjust charge as required.

Refer to Carrier Standard Service Techniques

Manual, Chapter 1, Refrigerants, for additional sys­

tem evacuation and dehydration instructions.

WEIGHT METHOD — Refer to Table 5 or unit

nameplate for correct system refrigerant charge.

Remove any refrigerant remaining in system before

recharging.