3. RECEPTACLES and CIRCUIT

BREAKERS

NOTICE - CLASS 1 WIRING METHODS ARE TO BE

USED FOR ALL FIELD WIRING CONNECTIONS TO

TERMINALS OF A CLASS 2 CIRCUIT. ALL WIRING

MUST BE DONE IN ACCORDANCE WITH

NATIONAL ELECTRIC CODE NFPA 70

A - 208/240 VOLT MAINLINE CIRCUIT BREAKER. This

is the low voltage mainline circuit breaker feeding the full

output terminal block (Ref E) below. This circuit breaker

is used when the selector switch in the 20/208 volt three

phase20/240 volt three phase or 20/240 volt single

phase switch position.

B - 480 VOLT MAINLINE CIRCUIT BREAKER. This is

the high voltage mainline circuit breaker feeding the full

output terminal block (Ref E) below. This circuit breaker

is used when the selector switch is in the 277/480 volt

three phase position.

C - CIRCUIT BREAKER LOCKING BAR. Select and

turn on either the high voltage breaker (480 V) or the low

voltage breaker (208 or 240 Volt) depending on which po-

sition you have the selector switch in. This bar prevents

both breakers from being turned on at the same time

D - REMOTE START/E-STOP TERMINAL BLOCK. This

terminal block provides the customer two different con-

nections.

Torque Screws to 9.6 in. lb. using 14 to 16

awg copper wire with lugs.

.

Emergency stop connection for installing a re-

mote emergency stop switch. This emergency stop

switch connection point must be closed during normal

operation, this is done at the factory by installing a

jumper lead between the two connection points. If

you have an application (i.e.. gas station) that re-

quires a remote stop switch be installed, remove the

jumper and install a normally closed emergency stop

switch between the two terminals. When the emer-

gency stop switch is opened the generator will imme-

diately shut down, requiring the switch to be reclosed

before the generator can be restarted.

2.

Remote start contact connections for starting the

unit from a remote location. This can be either

an automatic transfer switch or just a remote switch

in a job trailer. This feature requires a relay closure

between the two connections on the terminal block to

put the unit into an auto-start mode. The Auto mode

has both a start delay and a cooldown delay built into

the DSE-730.

E - FULL POWER OUTPUT TERMINAL BLOCK. The

full power terminal block is capable of handling full

generator output at any of the selected voltages. Be very

careful when using 240 volt three phase that you prop-

erly account for the wild leg (208 Volt) coming from the

generator.

This unit has it in the L2 position. For single

phase 20/240 connect to L and L3, the third leg L2 is

not powered or used.

Lugs will handle up to 2/0 wire.

Torque lugs to 150 in. lbs. using #1 & #2 wire and 180

in. lbs. for 1/0 & 2/0 wire.

RECEPTACLES

and CIRCUIT

BREAKERS