Winco RP25/C User Manual
Page 10
Page 8
60706-246
4200-00
F - NEUTRAL TERMINAL BLOCK. This is the neutral
connection point for the customers full power output
connections. This terminal block also has the neutral to
ground bond attached. If you need to operate an isolated
ground system this jumper must be removed. Generally
this is only required when the generator is being used as
backup or being wired into an existing wiring system that
already has one neutral to ground bond in it.
Lugs will
handle up to 2/0 wire. Torque lugs to 150 in. lbs. us-
ing #1 & #2 wire and 180 in. lbs. for 1/0 & 2/0 wire.
G - GROUND TERMINAL BLOCK. This is the ground
connection point for the customer's full power output
connections. This terminal block also has the neutral
to ground bond attached to it. If you need to operate an
isolated ground system this jumper must be removed.
Generally this is only required when the generator is be-
ing used as backup or being wired into an existing wiring
system that already has one neutral to ground bond in it.
Lugs will handle up to 2/0 wire. Torque lugs to 150
in. lbs. using #1 & #2 wire and 180 in. lbs. for 1/0 &
2/0 wire.
H - WIRE ENTRANCE HOLES. These hole have been
specifically provided for you to route your full power
leads through to the output lugs. The routing holes were
provided to insure that no small child or curious adult can
reach inside and come into contact with the main output
lugs with the unit running.
J - 120 VOLT 20 AMP 3 WIRE RECESSED SHORE
POWER PLUG, NEMA Spec 5-20. This panel mounted
plug is designed to plug directly in a standard 20 amp
receptacle on a extension cord. The plug when con-
nected will provide power to the block heater and the
battery trickle charger mounted inside the generator
enclosure. This can be used when the set is used in a
standby application to keep the engine warm and the
battery charged or in your rental yard to keep the battery
charged up. This receptacle is to be powered by a GFCI
circuit and installed in accordance with the United States
National Electric Code.
K - TWO - 120 VOLT 20 AMP GROUND FAULT
INTERRUPTER DUPLEX. These duplex receptacles are
protected by 20 Amp circuit breakers mounted just above
the duplexes. With the “T” slot design both 5 and 20
amp 20 volt cords can be plugged in.
L - 120 VOLT 20 AMP CIRCUIT BREAKERS. These
two push button 20 amp circuit breakers protect
the two
GFCI receptacles (Ref K) mounted below. If you are not
able to reset these breakers, check the load plugged into
the GFCI receptacle or the receptacle itself for a fault.
M - TWO 120/240 VOLT 50 AMP 4 WIRE TWISTLOCK.
These receptacles are rated for dual voltage, 20 or
240 volt use. It is a four wire receptacle, with a center
grounding pin. Four wire drop cords plugged into this
receptacle may be split into 20 volt receptacles at a dis-
tribution box. Each receptacle is protected by a two pole
50 amp circuit breaker mounted just above it.
THIS RECEPTACLE UTILIZES A HUBBELL PLUG PART
NUMBER “CS 6365”.
N - 250 VOLT 50 AMP CIRCUIT BREAKERS. These
circuit breakers protect the two 50 amp twistlock recep-
tacles (Ref M) mounted in the panel below.
P - DOOR SAFETY SWITCH. This safety switch is con-
nected to the DSE-730 engine control and will shut the
unit down any time door is opened with the unit running.
This prevents someone from accidently contacting the
main power connection with the unit running. This unit
will not start if the door is not closed and latched.
DANGER: PERSONAL INJURY
This unit may start as soon as the door is closed if the
engine control happen to be the correct mode. Do not
use the switch on this door to shutdown a unit to connect
to the full load terminal block , this is a safety switch only.
4. CAM-LOCK CONNECTIONS
This unit is equipped with Cam-Lock connectors, located
behind the rear right hand door panel. These Cam-Lock
are connected to the full load terminal blocks and a ca-
pable of providing full generator output in all voltage con-
figurations. The mating connectors are model CL2FB,
which are available with different wire size capabilities.