SERVICING BATTERIES

Batteries used on these units may over time lose water.

This is especially true if you are using a trickle charger

to maintain your battery. When refilling the battery with

water use only distilled water. Tap water will shorten the

service life of the battery.

Never fill the battery above the fill line. Over filling above

the upper level line may cause the electrolyte to overflow,

resulting in corrosion to the engine or nearby parts. Im-

mediately wash off any spilled electrolyte following the

procedure above..

CAUTION - NEVER ATTEMPT TO JUMP START THIS

ENGINE. If the battery should accidentally become

discharged disconnect the battery cables and recharge

the battery before attempting to start the unit. Boost/jump

starting this unit improperly will result in PERMANENT

DAMAGE TO THE ENGINE CONTROL MODULE (ECM).

DESCRIPTION AND IDENTIFICATION

1. ENGINE CONTROL MODULE (DSE7310)

The DSE-730 Automatic Start Control Module provides

integrated engine-genset control, protection, and meter-

ing in a single package. Microprocessor based technol-

ogy allows for exact measurement, set point adjustment,

and timing functions. Front panel controls and indicators

enable quick and simple DSE-730 operation. Deep Sea

communication software allows units to be easily custom-

ized for each application. A wide temperature-range liquid

crystal display (LCD) with backlighting can be viewed

under a wide range of ambient light and temperature

conditions.

FEATURES

DSE Generator Controllers have the following features:

• Five-key Menu Navigation

• Engine and Generator Protection

• Programmable Analog Engine Senders

• ECU Communications

• Programmable Logic

• Automatic Transfer Switch Control (Mains Failure)

• User Selectable RS232 & RS485 communications

• Multiple configurable inputs & outputs

• Event Log 250 events

• UL/CSA Listed

FUNCTIONS

DSE-730 Generator Controllers perform the following

functions:

Generator Protection and Metering

Generator protection guards against over voltage, under

voltage, under frequency, and over frequency. Over cur-

rent and phase imbalance protection is available as an

option at the time of manufacture. Each generator protec-

tion function has an adjustable pickup and time delay

setting. Metered generator parameters include voltage,

current, real power (watts), apparent power (VA), and

power factor (PF).