beautypg.com

50 cycle (hz) operation, Maintenance – Winco RP25/C User Manual

Page 14

background image

Page 2

60706-246

4200-00

6. If the transfer switch has a test button use it to test

the complete system. The unit should start up and

the transfer switch should transfer the load to the

generator.

7. Compare the amperage reading from each leg on the

generator and ensure that none of the legs is ex-

ceeding the nameplate rating on the generator.

8. Upon completion of the test, leave all control mode

switches in the “AUTO” position.

9. The system is now ready to start and power the loads

should the power fail.

F. CONNECTING THE LOADS FOR STAND ALONE

OPERATION

WARNING -ALL WIRING MUST BE DONE IN ACCOR-

DANCE WITH NATIONAL ELECTRIC CODE NFPA 70

There are three ways the loads may be connected to

Mobile Diesel Generator.

. FRONT PANEL - A variety of receptacles have been

provided for your convenience on the front panel.

The 20 volt receptacles are powered when the volt-

age selector switch is in the 20/240 single and three

phase and 20/208 three phase volt position. The

240 volt receptacles are only usable in the 20/240

volt single and three phase position. In the 20/208

volt three phase position the 240 volt receptacles

have only 208 volts at them. See table on page 9 for

voltage outputs.

2. FULL POWER LOAD CONNECTION TERMINAL

BLOCK - For remote connections and connecting

load distribution boxes, heavy duty terminal blocks

have been provided. These terminal blocks are

located on the rear of the unit just below the Engine

Contol. The neutral and ground are connected to-

gether at this panel. For use with an isolated neutral,

remove the jumper strap between the neutral con-

nection block and the ground lug. This will isolate

the neutral from the ground and allow you single

point grounding at a distribution panel. When using

these terminal blocks be sure to use wire rated large

enough to carry your full load or the full rated load of

the generator.

3. FULL POWER CAM-LOCK CONNECTIONS - For

ease of connecting and disconnecting loads these

units have been equipped with Cam-Locks located

behind the right hand rear door. See page 8 The

same instructions for connection #2 applies. If you

need to run a isolated neutral system, the jumper

between the neutral and ground must be removed at

the terminal block.

4. GROUNDING THE UNIT - To comply with current

safety standards this generator set must be properly

grounded. Ground the Mobile Diesel Generator set

by driving an 8 ft. copper ground rod into the earth.

Then connect a #4 AWG ground cable from the

grounding lug on the generator to the ground rod.

G. UNIT STORAGE

Certain precautions must be taken if a Mobile Diesel

Generator set is to be stored for a long period of time.

The unit must be stored in a dry location to prevent the

generator winding from drawing moisture. The unit should

also be thoroughly cleaned prior to storage.

For engine storage procedures consult your local Isuzu

engine dealer. There are procedures that must be fol-

lowed in order to prevent engine damage, i.e. cylinder

rust and injector deterioration.

50 CYCLE (HZ) OPERATION

With a couple of minor changes these Mobile Diesel

Generators are capable of producing 50 Hz power. Two

changes must be made:

A. The engine must be reduced to 500 RPM governed

speed. Consult your local Isuzu Service Center for the

proper procedure for reducing the engine speed and set-

ting up the governor to operate at 500 RPM.

B. The automatic volt/hertz regulator must also be reset

to operate at 50 HZ instead of the standard 60 HZ. Refer

to the Stamford generator manual for instructions.

MAINTENANCE

The ultimate aim of a preventive maintenance program is

to maintain the equipment in optimum condition, for the

maximum amount of time during it's useful life. The de-

tection of faults before they develop into major problems

will decrease downtime. A regular schedule of cleaning

and inspection will help assure trouble-free operation.

Personnel responsible for maintenance should set up a

schedule for inspection, and cleaning at intervals calcu-

lated to keep the equipment in good condition. In making

up a schedule, keep the following in mind:

A. New equipment must be carefully monitored until

extended operation has demonstrated that it is perform-

ing satisfactorily.
B. Old equipment requires more frequent inspection

(and possibly servicing) than similar equipment that has

lower hours
C. Time spent in cleaning, inspecting and correcting

minor defects before they become major troubles saves

time in overhaul and repair.