beautypg.com

Specifications, Preparation – Winco RP25/C User Manual

Page 4

background image

Page 2

60706-246

4200-00

SPECIFICATIONS

GENERATOR SPECIFICATIONS

RP25

KILOWATT

20 kW

KILOVOLT-AMPS (.8 PF)25 kVA

AMPERAGE 277/480 VOLT 3 PHASE 30 AMPS*

20/240 VOLT 3 PHASE 60 AMPS*

20/208 VOLT 3 PHASE 69 AMPS*

20/240 VOLT PHASE 70 AMPS**

*Based on .8 power factor

**Single Phase is limited by the circuit breaker to 50

Amps on the full power terminal block - The

addtional amperage is available through receptacles.

Derate 3% per 000 feet (305 meters) between 300 feet

(90 meters) and 7,500 feet (2,286 meters) above sea

level. Contact the factory for rating data for operation in

altitudes above 7,500 feet (2,286 meters).

For prime power application (24/7) derate all output rating

by 0%

GENERATOR RESISTANCE

RP25

Generator Make

Stamford

Generator Model

PI44F

Generator Winding

#3

Voltage Regulator

AS480

Main Stator

0.265 ohms

Main Rotor

0.708 ohms

Exciter Stator

20.3 ohms

Exciter Rotor

0.20 ohms

ENGINE SPECIFICATIONS

RP25/B

Make

Isuzu

Model

4LE

Fuel Consumption

Full Load .9 gal/hr

/2 Load .9 gal/hr

Starting System

2 Volt DC

Fuel

Diesel

Oil

API CF - CH4

SAE 0W30

8.69 Liters

Oil & Filter Replacement

250 HRS

Coolant

50/50 Mix

2.75 Gallons

Battery 12 Volt (Group 24)

650 CCA*

*Battery is not included.

TRAILER/HOUSING

RP25

Capacity

3500 lb.

Fuel Capacity

55 Gallons

Axles

Single

Hitch Height

Adjustable

Tires

P225/75R-5

Tire Pressure

35 psi

Sound Attenuated

ULTRA QUIET

Housing

Housing Standard

PREPARATION

NOTE: This booklet covers the entire unit, EXCEPT

THE ENGINE. See the engine manufacturer’s operator

manual for specific maintenance and care information re-

garding the engine. Read ALL instructions in the manuals

provided before attempting to operate the generator set.

UNPACKING

When receiving the unit, be sure to inspect it carefully

for freight loss or damage. Check the nameplate to be

sure it is what you ordered (proper kW, voltage, fuel,

etc.). If you have questions, contact your local authorized

dealer. If you see evidence of loss or damage at the time

of delivery, have the driver sign and describe the loss or

damage in the “memo of loss or damage” section on the

freight bill. Then contact the carrier to get instructions on

filing a claim.

When loss or damage is discovered after the equipment

is delivered, but not seen at the time of delivery, it is re-

ferred to as “concealed damage.” Separate any damaged

material and contact the carrier for proper procedures to

file a “concealed damage” claim.

OIL REQUIREMENTS

This engine was filled at the factory. Before starting

check the oil level and ensure it is full. If not, refill to the

proper level. See engine manual for proper grade of oil.

OIL QUANTITY

US Qt.

Liters

RP25

9

8.7

FUEL REQUIREMENTS

See your engine operator's manual for complete type and

fuel grade information.

WARNING -NO BIODIESEL

Filling the Fuel Tank

Standard Trailer - The standard trailer is equipped with

a single 45 gallon fuel tank. Use caution when filling the

tank so as not to overflow the tank into the trailer.