Winco RP25/C User Manual
Page 11

Page 9
4200-00
60706-246
VOLTAGE SELECTOR SWITCH
POSITION
TERMINALS MINIMUM
VOLTAGE
NORMAL
VOLTAGE
MAXIMUM
VOLTAGE
120/240 SINGLE PHASE
LINE TO LINE
L TO L3
220
240
260
20/240 VOLT RECEPTACLES
0/220
20/240
30/260
LINE TO NEUTRAL
L TO N
0
20
30
L2 TO N
-0-
-0-
-0-
L3 TO N
0
20
30
20 VOLT RECEPTACLES
0
20
30
120/208 THREE PHASE
LINE TO LINE
ALL
200
208
220
20/240 VOLT RECEPTACLES
0/200
20/208
27/220
LINE TO NEUTRAL
ALL
5
20
27
20 VOLT RECEPTACLES
ALL
5
20
27
G3 TO N
5
20
27
120/240 THREE PHASE
LINE TO LINE
ALL
220
240
260
20/240 VOLT RECEPTACLES
0/220
20/240
30/260
LINE TO NEUTRAL
USE CAUTION THIS CONFIGU-
RATION HAS A HIGH VOLTAGE
LEG
G TO N
0
20
30
HIGH VOLTAGE LEG
G2 TO N
9
208
225
G3 TO N
0
20
30
20 VOLT RECETPACLES
0
20
30
277/480 THREE PHASE
LINE TO LINE
ALL
46
460
480
20/240 VOLT RECEPTACLE
NONE
NONE
NONE
LINE TO NEUTRAL
ALL
240
265
277
20 VOLT RECETPACLE
NONE
NONE
NONE
The table below show the voltages at the terminal lug as well as the receptacles
for all four voltage patterns available through the selector switch.
WARNING - POTENTIAL EQUIPMENT DAMAGE
THE 120/240 VOLT THREE PHASE POSITION HAS A WILD LEG THAT PRODUCES 208 VOLTS LINE TO
NEUTRAL ON G2. BE SURE WHEN CONNECTING TO YOUR PANEL OR LOAD THAT YOU MATCH THE
WILD PHASE ON THE GENERATOR TO THE WILD PHASE IN YOUR PANEL OR LOAD. FAILURE TO DO
SO WILL RESULT IN 12O VOLT DEVICES RECEIVING 208 VOLTS. YOU MUST ALSO MATCH YOUR
ROTATION.