beautypg.com

Winco RP25/C User Manual

Page 11

background image

Page 9

4200-00

60706-246

VOLTAGE SELECTOR SWITCH

POSITION

TERMINALS MINIMUM

VOLTAGE

NORMAL

VOLTAGE

MAXIMUM

VOLTAGE

120/240 SINGLE PHASE
LINE TO LINE

L TO L3

220

240

260

20/240 VOLT RECEPTACLES

0/220

20/240

30/260

LINE TO NEUTRAL

L TO N

0

20

30

L2 TO N

-0-

-0-

-0-

L3 TO N

0

20

30

20 VOLT RECEPTACLES

0

20

30

120/208 THREE PHASE
LINE TO LINE

ALL

200

208

220

20/240 VOLT RECEPTACLES

0/200

20/208

27/220

LINE TO NEUTRAL

ALL

5

20

27

20 VOLT RECEPTACLES

ALL

5

20

27

G3 TO N

5

20

27

120/240 THREE PHASE
LINE TO LINE

ALL

220

240

260

20/240 VOLT RECEPTACLES

0/220

20/240

30/260

LINE TO NEUTRAL

USE CAUTION THIS CONFIGU-

RATION HAS A HIGH VOLTAGE

LEG

G TO N

0

20

30

HIGH VOLTAGE LEG

G2 TO N

9

208

225

G3 TO N

0

20

30

20 VOLT RECETPACLES

0

20

30

277/480 THREE PHASE
LINE TO LINE

ALL

46

460

480

20/240 VOLT RECEPTACLE

NONE

NONE

NONE

LINE TO NEUTRAL

ALL

240

265

277

20 VOLT RECETPACLE

NONE

NONE

NONE

The table below show the voltages at the terminal lug as well as the receptacles

for all four voltage patterns available through the selector switch.

WARNING - POTENTIAL EQUIPMENT DAMAGE

THE 120/240 VOLT THREE PHASE POSITION HAS A WILD LEG THAT PRODUCES 208 VOLTS LINE TO

NEUTRAL ON G2. BE SURE WHEN CONNECTING TO YOUR PANEL OR LOAD THAT YOU MATCH THE

WILD PHASE ON THE GENERATOR TO THE WILD PHASE IN YOUR PANEL OR LOAD. FAILURE TO DO

SO WILL RESULT IN 12O VOLT DEVICES RECEIVING 208 VOLTS. YOU MUST ALSO MATCH YOUR

ROTATION.