Engine Protection and Metering
Engine protection features include oil pressure and cool-
ant temperature monitoring, over crank protection, ECU
specific protection elements, and diagnostic reporting.
Metered engine parameters include, oil pressure, coolant
temperature, battery voltage, speed, fuel level, engine
load, coolant level (from ECU), ECU specific parameters,
and run-time statistics.
All metering functions are displayed on the liquid crystal
display. The front panel display begins with the SUMMA-
RY SCREEN. Pressing the Right arrow key will open the
MAIN MENU screen. The MAIN MENU screen consists
of METERING and SETTINGS
DSE 7310 CONTROLLER LAYOUT
A. MENU NAVIGATION BUTTONS – Left and Right but-
tons select different grouping (i.e. Engine reading Gen-
erator reading, etc). Up and Down buttons scroll through
the different reading for each group.
B. STOP/RESET – This button places the module into its
STOP/RESET mode. This will clear any alarm conditions
for which the triggering criteria have been removed. If
the engine is running and this button is pushed the mod-
ule will shut off the fuel solenoid and the engine will come
to a stop. If a remote start signal is received while this
switch is activated, the unit will not start.
C. MANUAL - This mode allows manual control of the
generator functions. Once in this mode the control mod-
ule will allow you to start the unit using the START button.
The unit will continue to run until either the STOP/RESET
or AUTO button is pressed. If the unit receives a remote
start signal during manual operation, the generator will
remain running even after the remote start signal has
been lost. You must use the STOP/RESET or AUTO but-
ton to stop the unit once you have started it in MANUAL
mode.
**** CAUTION ****
IF THE POWER FAILS WHILE RUNNING IN THE MAN-
UAL MODE THE TRANSFER SWITCH WILL TRANS-
FER THE LOAD TO THE GENERATOR. TO PREVENT
THIS THE MAINLINE CIRCUIT BREAKER ON THE
GENERATOR MUST BE OPENED.
D. AUTO – This button places the module into its AUTO-
MATIC mode. This module will monitor the remote start
input for a relay closure. When the remote start signal is
received it will time out the start delay (5 Seconds) and
then start the engine generator set. When the remote
start signal is lost (relay opened) the module will shut
the engine generator set down after the cool down timer
has time out. The module will return to the AUTOMATIC
mode and await the next start signal.
E. LAMP TEST/HORN RESET - This button silences
the audible alarm if it is sounding and illuminates all of
the LEDs as a lamp test feature.
F. START – This button is active only in the MANUAL
or mode. Pressing this button in the MANUAL mode will
start the engine locally for testing. The engine will con-
tinue to run until either the STOP/RESET or the AUTO
button is pressed.
G. CLOSE GEN-SET – NOT USED IN THIS APPLICA-
TION
H. OPEN GEN-SET – NOT USED IN THIS APPLICA-
TION
J. SYSTEM INFORMATION LIGHTS – These lights indi-
cate the following conditions.
. Low Battery
2. Low Fuel
3. Generator Available
4. Emergency Stop.
K. LIQUID CRYSTAL DISPLAY (LCD) -A wide tempera-
ture-range display with backlighting can be viewed under
a wide range of ambient light and temperature conditions.
All engine and generator reading are displayed here,
including fault codes.
NOTE: STOP/RESET, MANUAL mode and AUTO mode
buttons all have indicator lamps next to them to tell you
what mode you are in. Pressing buttons out of sequence
will cause the engine not to do what you may think it
should be doing. See button operation sequencing
above.