Engine Protection and Metering

Engine protection features include oil pressure and cool-

ant temperature monitoring, over crank protection, ECU

specific protection elements, and diagnostic reporting.

Metered engine parameters include, oil pressure, coolant

temperature, battery voltage, speed, fuel level, engine

load, coolant level (from ECU), ECU specific parameters,

and run-time statistics.

All metering functions are displayed on the liquid crystal

display. The front panel display begins with the SUMMA-

RY SCREEN. Pressing the Right arrow key will open the

MAIN MENU screen. The MAIN MENU screen consists

of METERING and SETTINGS

DSE 7310 CONTROLLER LAYOUT

A. MENU NAVIGATION BUTTONS – Left and Right but-

tons select different grouping (i.e. Engine reading Gen-

erator reading, etc). Up and Down buttons scroll through

the different reading for each group.

B. STOP/RESET – This button places the module into its

STOP/RESET mode. This will clear any alarm conditions

for which the triggering criteria have been removed. If

the engine is running and this button is pushed the mod-

ule will shut off the fuel solenoid and the engine will come

to a stop. If a remote start signal is received while this

switch is activated, the unit will not start.

C. MANUAL - This mode allows manual control of the

generator functions. Once in this mode the control mod-

ule will allow you to start the unit using the START button.

The unit will continue to run until either the STOP/RESET

or AUTO button is pressed. If the unit receives a remote

start signal during manual operation, the generator will

remain running even after the remote start signal has

been lost. You must use the STOP/RESET or AUTO but-

ton to stop the unit once you have started it in MANUAL

mode.

**** CAUTION ****

IF THE POWER FAILS WHILE RUNNING IN THE MAN-

UAL MODE THE TRANSFER SWITCH WILL TRANS-

FER THE LOAD TO THE GENERATOR. TO PREVENT

THIS THE MAINLINE CIRCUIT BREAKER ON THE

GENERATOR MUST BE OPENED.

D. AUTO – This button places the module into its AUTO-

MATIC mode. This module will monitor the remote start

input for a relay closure. When the remote start signal is

received it will time out the start delay (5 Seconds) and

then start the engine generator set. When the remote

start signal is lost (relay opened) the module will shut

the engine generator set down after the cool down timer

has time out. The module will return to the AUTOMATIC

mode and await the next start signal.

E. LAMP TEST/HORN RESET - This button silences

the audible alarm if it is sounding and illuminates all of

the LEDs as a lamp test feature.

F. START – This button is active only in the MANUAL

or mode. Pressing this button in the MANUAL mode will

start the engine locally for testing. The engine will con-

tinue to run until either the STOP/RESET or the AUTO

button is pressed.

G. CLOSE GEN-SET – NOT USED IN THIS APPLICA-

TION

H. OPEN GEN-SET – NOT USED IN THIS APPLICA-

TION

J. SYSTEM INFORMATION LIGHTS – These lights indi-

cate the following conditions.

. Low Battery

2. Low Fuel

3. Generator Available

4. Emergency Stop.

K. LIQUID CRYSTAL DISPLAY (LCD) -A wide tempera-

ture-range display with backlighting can be viewed under

a wide range of ambient light and temperature conditions.

All engine and generator reading are displayed here,

including fault codes.

NOTE: STOP/RESET, MANUAL mode and AUTO mode

buttons all have indicator lamps next to them to tell you

what mode you are in. Pressing buttons out of sequence

will cause the engine not to do what you may think it

should be doing. See button operation sequencing

above.