8table 2 — electric heating capacities – Carrier 50TFQ008-012 User Manual
Page 8
8
Table 2 — Electric Heating Capacities
*Two heater packages required to provide kW indicated.
†Use CRSINGLE008A00 for units with an electrical convenience outlet.
NOTES:
1. The rated heater voltage is 240, 480, and 575 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the following formula:
Heater kW new = Heater kW rated x (unit power distribution voltage/rated heater voltage)
2
As an example:
For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v
kW new = 16 kW (215/240)
2
kW new = 12.8 kW (rating at 215 v)
Table 3A — Electrical Data (Units Without Electrical Convenience Outlet)
NOTE: Legend and Notes for Electrical Data are on page 11.
50TFQ
UNIT SIZE
UNIT VOLTAGE
(60 Hz)
ACCESSORY
kW
ELECTRIC HEATER
PART NUMBER
CRHEATER---A00
SINGLE POINT BOX
PACKAGE NO.
CRSINGLE---A00
008, 009
208/230/240
(3 phase)
7.8/ 9.6/10.4
12.0/14.7/16.0
18.6/22.8/24.8
24.0/29.4/32.0
31.8/39.0/42.4*
017
010
011
012
012 and 017
007
007
009
009
013
460/480
(3 phase)
12.8/13.9
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
016
013
014
015
014 and 016
006
006
008
008
010
575
(3 phase)
17.0
34.0
018
019
006
006†
012
208/230/240
(3 phase)
7.8/ 9.6/10.4
12.0/14.7/16.0
24.0/29.4/32.0
31.8/39.0/42.4*
37.6/46.2/50.0*
017
010
012
012 and 017
010 and 012
012
012
015
017
017
460/480
(3 phase)
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
45.9/50.0*
013
014
015
014 and 016
013 and 015
011
014
014
016
016
575
(3 phase)
17.0
34.0
51.0*
018
019
018 and 019
011
014
016
50TFQ
UNIT SIZE
NOMINAL
V-PH-Hz
IFM
TYPE
VOLTAGE
RANGE
COMPRESSOR
(each)
OFM
FLA
IFM
FLA
ELECTRIC HEAT*
POWER SUPPLY
DISCONNECT
SIZE†
Min Max
RLA
LRA
Nominal
kW**
FLA
MCA
MOCP
FLA
LRA
008
(7
1
/
2
Tons)
208/230-3-60
STD
187
254
13.4
91.0
1.4
5.8
—
—
38.8/ 38.8
40/ 40††
41/ 41
229/229
7.8/10.4
21.7/ 25.0
65.9/ 70.0
70/ 70
66/ 69
251/254
12.0/16.0
33.3/ 38.5
80.4/ 86.9
90/ 90
79/ 85
262/268***
18.6/24.8
51.6/ 59.7
103.3/113.4
110/125
100/109
281/289***
24.0/32.0
66.6/ 77.0
122.0/135.0
125/150
117/129
296/306***
31.8/42.4
88.3/102.0
149.1/166.3
150/175
142/158
317/331***
HIGH-STATIC
187
254
13.4
91.0
1.4
10.6
—
—
43.6/ 43.6
45/ 45††
46/ 46
273/273
7.8/10.4
21.7/ 25.0
70.7/ 74.8
80/ 80
71/ 75
294/298
12.0/16.0
33.3/ 38.5
85.2/ 91.7
90/100
85/ 91
306/311***
18.6/24.8
51.6/ 59.7
108.1/118.2
110/125
106/115
324/332***
24.0/32.0
66.6/ 77.0
126.8/139.8
150/150
123/135
339/350***
31.8/42.4
88.3/102.0
153.9/171.1
175/175
148/164
361/375***
460-3-60
STD
414
508
6.7
42.0
0.7
2.6
—
—
19.1
20††
20
108
13.9
16.7
40.0
40††
39
124
16.5
19.8
43.8
45††
43
128
27.8
33.4
60.8
70
58
141
33.0
39.7
68.7
70
66
147
41.7
50.2
81.8
90
78
158
HIGH-STATIC
414
508
6.7
42.0
0.7
4.8
—
—
21.3
25††
23
130
13.9
16.7
42.2
45††
42
146
16.5
19.8
46.0
50††
45
149
27.8
33.4
63.0
70
61
163
33.0
39.7
70.9
80
68
169
41.7
50.2
84.0
90
80
180***
575-3-60
STD
518
632
5.4
39.0
0.7
2.6
—
—
15.4
20††
16
97
17.0
17.1
36.7
40††
36
114
34.0
34.1
58.0
60††
55
131
HIGH-STATIC
4.8
—
—
17.1
20††
18
114
17.0
17.1
38.5
40††
38
132
34.0
34.1
59.7
60††
57
149