Carrier 50TFQ008-012 User Manual

Page 11

background image

11

Table 3B — Electrical Data (Units With Electrical Convenience Outlet) (cont)

LEGEND

*Heaters are field installed only.

†Used to determine minimum disconnect size per NEC.

**Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v. If

power distribution voltage to unit varies from rated heater voltage, heater kW will vary
accordingly.

††Fuse or HACR circuit breaker.

***Optional disconnect switch is unavailable.

NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment

(refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall
be fuse or HACR breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percent of voltage imbalance.

% Voltage Imbalance

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable
2%.

50TFQ

UNIT SIZE

NOMINAL

V-PH-Hz

IFM

TYPE

VOLTAGE

RANGE

COMPRESSOR

(each)

OFM

FLA

IFM

FLA

ELECTRIC

HEAT*

POWER SUPPLY

DISCONNECT

SIZE†

Min

Max

RLA

LRA

Nominal

kW**

FLA

MCA

MOCP

FLA

LRA

012

(10 Tons)

208/230-3-60

STD

187

254

17.2

124.0

1.4

5.8

52.1/ 52.1

60/ 60††

55/ 55

300/300

7.8/10.4

21.7/ 25.0

79.2/ 83.4

80/ 90

80/ 84

322/325***

12.0/16.0

33.3/ 38.5

93.7/100.2

100/110

93/ 99

333/338***

24.0/32.0

66.6/ 77.0

135.4/148.4

150/150

132/144

366/377***

31.8/42.4

88.3/102.0

162.5/179.6

175/200

157/172

388/402***

37.6/50.0

104.4/120.3

182.6/172.4

200/200

175/193

404/420***

ALT

187

254

17.2

124.0

1.4

7.5

53.8/ 53.8

60/ 60††

57/ 57

319/319

7.8/10.4

21.7/ 25.0

80.9/ 85.1

90/ 90

82/ 86

341/344***

12.0/16.0

33.3/ 38.5

95.4/101.9

100/110

95/101

352/357***

24.0/32.0

66.6/ 77.0

137.1/150.1

150/175

134/145

385/396***

31.8/42.4

88.3/102.0

164.2/181.3

175/200

158/174

407/421***

37.6/50.0

104.4/120.3

184.3/174.1

200/200

177/195

423/439***

HIGH-STATIC

187

254

17.2

124.0

1.4

15.0

61.3/ 61.3

70/ 70

66/ 66

367/367

7.8/10.4

21.7/ 25.0

88.4/ 92.6

90/100

91/ 94

389/392***

12.0/16.0

33.3/ 38.5

102.9/109.4

110/110

104/110

400/405***

24.0/32.0

66.6/ 77.0

144.6/157.6

150/175

142/154

433/444***

31.8/42.4

88.3/102.0

171.7/188.8

175/200

167/183

455/459***

37.6/50.0

104.4/120.3

191.8/181.6

200/200

186/204

471/487***

460-3-60

STD

414

508

8.6

59.6

0.7

2.6

25.5

30††

27

145

16.5

19.8

50.3

60††

50

165

27.8

33.4

67.3

70

65

178

33.0

39.7

75.2

80

73

185

41.7

50.2

88.3

90

85

195***

50.0

60.1

85.6

90

96

205***

ALT

414

508

8.6

59.6

0.7

3.4

26.3

30††

28

185

16.5

19.8

51.1

60††

51

204

27.8

33.4

68.1

70

66

218

33.0

39.7

76.0

80

73

224

41.7

50.2

89.1

90

86

235***

50.0

60.1

86.4

90

97

245***

HIGH-STATIC

414

508

8.6

59.6

0.7

7.4

30.3

35††

32

179

16.5

19.8

55.1

60††

55

198

27.8

33.4

72.1

80

71

212

33.0

39.7

80.0

80

78

218

41.7

50.2

93.1

100

90

229***

50.0

60.1

90.4

100

102

239***

575-3-60

STD

518

632

6.9

49.4

0.7

2.6

20.5

25††

22

120

17.0

17.1

41.8

45††

41

137

34.0

34.1

63.1

70

61

154

51.0

51.2

71.7

80

80

171***

ALT

518

632

6.9

49.4

0.7

3.4

21.1

25††

22

151

17.0

17.1

42.5

45††

42

168

34.0

34.1

63.7

70

62

185

51.0

51.2

72.3

80

81

202***

HIGH-STATIC

518

632

6.9

49.4

0.7

7.4

24.3

25††

26

146

17.0

17.1

45.7

50††

46

163

34.0

34.1

66.9

70

65

180

51.0

51.2

75.5

80

85

198***

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor Fan Motor

RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local
electric utility company immediately.

7

457