Step 7 — adjust indoor-fan speed – Carrier 50TFQ008-012 User Manual

Page 25

background image

25

CO

2

sensor to the actuator when the CO

2

concentration in the

space is at 1100 ppm. The DCV set point may be left at 2 volts
since the CO

2

sensor voltage will be ignored by the

EconoMi$er IV controller until it rises above the 3.6 volt set-
ting of the minimum position potentiometer.

Once the fully occupied damper position has been deter-

mined, set the maximum damper demand control ventilation
potentiometer to this position. Do not set to the maximum posi-
tion as this can result in over-ventilation to the space and poten-
tial high-humidity levels.
CO

2

Sensor Configuration — The CO

2

sensor has preset

standard voltage settings that can be selected anytime after the
sensor is powered up. See Table 8.

Use setting 1 or 2 for Carrier equipment. See Table 8.

1. Press Clear and Mode buttons. Hold at least 5 seconds

until the sensor enters the Edit mode.

2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number. See

Table 8.

4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.

The custom settings of the CO

2

sensor can be changed any-

time after the sensor is energized. Follow the steps below to
change the non-standard settings:

1. Press Clear and Mode buttons. Hold at least 5 seconds

until the sensor enters the Edit mode.

2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD menu

and press Enter.

4. Use the Up/Down button to toggle through each of the

nine variables, starting with Altitude, until the desired set-
ting is reached.

5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode to

continue to the next variable.

Dehumidification of Fresh Air with DCV Control — Infor-
mation from ASHRAE indicates that the largest humidity load
on any zone is the fresh air introduced. For some applications,
a device such as a 62AQ energy recovery unit is added to re-
duce the moisture content of the fresh air being brought into the

building when the enthalpy is high. In most cases, the normal
heating and cooling processes are more than adequate to re-
move the humidity loads for most commercial applications.

If normal rooftop heating and cooling operation is not ade-

quate for the outdoor humidity level, an energy recovery unit
and/or a dehumidification option should be considered.

Step 7 — Adjust Indoor-Fan Speed —

Adjust the

indoor-fan speed to meet jobsite conditions.

For units with electric heat, required minimum cfm is 2250

for 50TFQ008, 2550 for 50TFQ009 and 3000 for 50TFQ012
with the following exceptions:

Table 9 shows indoor-fan motor data. Table 10 shows fan

rpm at motor pulley settings for standard and alternate motors.
Tables 11A and 11B show static pressure for accessories. Refer
to Tables 12-27 to determine fan speed settings. Fan motor
pulleys are factory set for speed shown in Table 1.
To change fan speeds:

1. Shut off the unit power supply and tag disconnect.
2. Loosen the belt by loosening the fan motor mounting

nuts. See Fig. 38 and 39.

3. Loosen the movable pulley flange setscrew (see Fig. 40).
4. Screw the movable flange toward the fixed flange to

increase speed or away from the fixed flange to decrease
speed. Increasing the fan speed increases the load on the
motor. Do not exceed the maximum speed specified in
Table 1.

5. Set the movable flange at nearest keyway of the pulley

hub and tighten the setscrew. (See Table 1 for speed
change for each full turn of the pulley flange.)

Table 8 — CO

2

Sensor Standard Settings

LEGEND

ppm — Parts Per Million

UNIT

UNIT

VOLTAGE

HEATER

kW

UNIT

CONFIG-

URATION

REQUIRED

MINIMUM

CFM

50TFQ012

208/230

42.4

Horizontal

3200

208/230

50.0

Horizontal

3200

460

50.0

Horizontal or

Vertical

3200

575

17.0

Horizontal or

Vertical

2800

51.0

2350

SETTING

EQUIPMENT

OUTPUT

VENTILATION

RATE

(cfm/Person)

ANALOG

OUTPUT

CO

2

CONTROL RANGE

(ppm)

OPTIONAL

RELAY SETPOINT

(ppm)

RELAY

HYSTERESIS

(ppm)

1

Interface w/Standard
Building Control System

Proportional

Any

0-10V

4-20 mA

0-2000

1000

50

2

Proportional

Any

2-10V

7-20 mA

0-2000

1000

50

3

Exponential

Any

0-10V

4-20 mA

0-2000

1100

50

4

Economizer

Proportional

15

0-10V

4-20 mA

0-1100

1100

50

5

Proportional

20

0-10V

4-20 mA

0- 900

900

50

6

Exponential

15

0-10V

4-20 mA

0-1100

1100

50

7

Exponential

20

0-10V

4-20 mA

0- 900

900

50

8

Health & Safety

Proportional

0-10V

4-20 mA

0-9999

5000

500

9

Parking/Air Intakes/
Loading Docks

Proportional

0-10V

4-20 mA

0-2000

700

50