START-UP CHECKLIST

(Remove and Store in Job File)

I. PRELIMINARY INFORMATION

MODEL NO.: __________________________________

SERIAL NO.: ______________________________________

DATE: ________________________________________

TECHNICIAN: _____________________________________

BUILDING LOCATION: _________________________

II. PRE-START-UP (insert checkmark in box as each item is completed)

VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS

CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS

CHECK THAT RETURN (INDOOR) AIR FILTERS ARE CLEAN AND IN PLACE

VERIFY THAT UNIT INSTALLATION IS LEVEL

CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW
TIGHTNESS

CHECK PULLEY ALIGNMENT AND BELT TENSION PER INSTALLATION INSTRUCTIONS

VERIFY INSTALLATION OF ECONOMIZER HOOD (IF EQUIPPED)

III. START-UP:

ELECTRICAL

TEMPERATURES

PRESSURES (COOLING MODE)

VERIFY THAT 3-PHASE SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION (SIZE 012 ONLY)
VERIFY REFRIGERANT CHARGE USING COOLING CHARGING CHARTS ON PAGES 48 AND 49.

GENERAL

SET ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO MATCH JOB REQUIREMENTS
(IF EQUIPPED)

SUPPLY VOLTAGE

L1-L2

L2-L3

L3-L1

CIRCUIT 1 COMPRESSOR AMPS L1

L2

L3

CIRCUIT 2 COMPRESSOR AMPS L1

L2

L3

INDOOR-FAN AMPS

L1

L2

L3

OUTDOOR-AIR TEMPERATURE

DB

WB

RETURN-AIR TEMPERATURE

DB

WB

COOLING SUPPLY AIR

DB

WB

REFRIGERANT SUCTION, CIRCUIT 1

PSIG

F

REFRIGERANT SUCTION, CIRCUIT 2

PSIG

F

REFRIGERANT DISCHARGE, CIRCUIT 1

PSIG

F

REFRIGERANT DISCHARGE, CIRCUIT 2

PSIG

F