beautypg.com

Fig. 24 — outdoor-air hood construction, Fig. 25 — filter installation, Fig. 26 — economi$er iv wiring – Carrier 50TFQ008-012 User Manual

Page 19

background image

19

6. Insert the hood divider between the hood sides. See

Fig. 24 and 25. Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the bot-
tom filter rack for the aluminum filter.

7. Open the filter clips which are located underneath the

hood top. Insert the aluminum filter into the bottom filter
rack (hood divider). Push the filter into position past the
open filter clips. Close the filter clips to lock the filter into
place. See Fig. 25.

8. Caulk the ends of the joint between the unit top panel and

the hood top. See Fig. 23.

9. Replace the filter access panel.

10. Install all EconoMi$er IV accessories. EconoMi$er IV

wiring is shown in Fig. 26. EconoMi$er2 wiring is shown
in Fig. 27.

Barometric flow capacity is shown in Fig. 28. Outdoor air

leakage is shown in Fig. 29. Return air pressure drop is shown
in Fig. 30.

B

TOP
PANEL

INDOOR COIL
ACCESS PANEL

24 9/16”

SCREW

HOOD DIVIDER

LEFT
HOOD
SIDE

40 3/8”

Fig. 24 — Outdoor-Air Hood Construction

22 1/4”

DIVIDER

BAROMETRIC
RELIEF

CLEANABLE
ALUMINUM
FILTER

FILTER

HOOD

FILTER
CLIP

OUTSIDE
AIR

Fig. 25 — Filter Installation

FOR OCCUPANCY CONTROL
REPLACE JUMPER WITH
FIELD-SUPPLIED TIME CLOCK

LEGEND

DCV— Demand Controlled Ventilation
IAQ — Indoor Air Quality
LA — Low Ambient Lockout Device
OAT — Outdoor-Air Temperature
POT — Potentiometer
RAT — Return-Air Temperature

Potentiometer Defaults Settings:
Power Exhaust

Middle

Minimum Pos.

Fully Closed

DCV Max.

Middle

DCV Set

Middle

Enthalpy

C Setting

NOTES:

1. 620 ohm, 1 watt 5% resistor should be removed only when using differential

enthalpy or dry bulb.

2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power

supply, it cannot have the secondary of the transformer grounded.

3. For field-installed remote minimum position POT, remove black wire jumper

between P and P1 and set control minimum position POT. to the minimum
position.

Fig. 26 — EconoMi$er IV Wiring