4-8 Compaq 2000 Series UPS Operation and Reference Guide

Figure 4-4. Optimal—Utility voltage fluctuating within the UPS operating
range

Operating Range

Utility Voltage

+ 20%

- 20%

Time

V

oltage

Nominal

Figure 4-5. Utility voltage fluctuation indicating a shift in nominal voltage
range may be necessary

Operating Range

Utility Voltage

+20%

- 20%

-35%

Time

V

oltage

Nominal

Extended

Range

Figure 4-6. Utility voltage fluctuation indicating a possible need for
extended range setting

To match the utility voltage, the UPS operating range can be modified in two
ways:

If the utility voltage differs from the currently configured nominal
voltage, but stays within a ±20% band (see Fig 4-5), consider shifting
the nominal voltage parameter selection to match the measured utility
voltage range.