beautypg.com

Compaq 2000 User Manual

Page 36

background image

3-6 Compaq 2000 Series UPS Operation and Reference Guide

Site Wiring Fault (LED 5)

Table 3-2

Site Wiring Fault LED

LED

Color

Meaning

5

Red

No ground connection between utility power and the UPS.

The line and neutral connections between utility power and the
UPS are reversed.

The UPS voltage configuration may be incorrect.

Note: For units factory-configured for 208V, the Site Wiring Fault function has been
disabled. If reconfiguring a 230V unit to operate at 208V, the Site Wiring Fault function
must be manually disabled. See the section “Changing Configuration Parameters” in
Chapter 4, “Configuration.”

Battery Charge (LEDs 6-9)

Table 3-3

Battery Charge LEDs

LED

Color

Meaning

6

Green

Batteries are between 67% and 100% charged.
(LEDs 7 and 8 are also green)

7

Green

Batteries are approximately 66% charged.
(LED 8 is also green)

8

Green

Batteries are approximately 33% charged.

9

Red

Batteries are low; approximately three to five minutes of battery
backup remain.

Battery Service (LED 10)

Table 3-4

Battery Service LED

LED

Color

Meaning

10

Red

Potential battery failure.

Note: When LED 10 is red, the audio alarm will sound, indicating the UPS has detected a
potential battery failure. The UPS batteries may need to be replaced in 30 to 60 days.