beautypg.com

Slant/Fin HWT-120 User Manual

Page 3

background image

3

INDIRECT FIRED WATER TANK

b. Estimate unusual peak draw demand. Whirlpool baths, hot tubs, and mutltiple head showers require large
quantities of hot water in a short period of time. Contact fixture manufacturer for quantity of water required.

Generally speaking, these circumstances can only be met with larger storage volumes.

c. Domestic Water Temperature. Most residential usage will be satisfied with 119˚F water, the temperature
setting recommended by the Consumer Product Safety Commission. Some applications such as laundry and

dishwashers may require a higher temperature.

Ratings can be improved by increasing thermostat setting and using a mixing valve to temper the hot water to

the proper temperature. When temperatures greater than 119˚F are required, use a mixing valve at the outlet of

the water heater or anti-scald fittings at point of use.

II PRODUCT SELECTION / PERFORMANCE

1. The following guidelines apply to residential systems only. For commercial or institutional installations contact the

factory directly for assistance.

2. Determine the quantity of domestic hot water required. Factors to consider:

a. Estimate typical peak hour demand. Determine the general time of day (morning, noon, evening) when
the most hot water is used. Use chart below to determine potential maximum usage.

Estimate of Peak Domestic Hot Water Usage

Shower

20

x ______________________

=

x_______________________

Bath

20

x ______________________

=

x_______________________

Shaving

2

x ______________________

=

x_______________________

Hands and Face Washing

4

x ______________________

=

x_______________________

Hair Shampoo

4

x ______________________

=

x_______________________

Hand Dish Washing

4

x ______________________

=

x_______________________

Automatic Dish Washing

14

x ______________________

=

x_______________________

Food Preparation

5

x ______________________

=

x_______________________

Wringer Clothes Washer

26

x ______________________

=

x_______________________

Automatic Clothes Washer

32

x ______________________

=

x_______________________

Total Peak Hour Demand

=

_______________________

Average Gallons of
Use Hot Water per Usage

Use

Times Used During

One Hour

Times Used During

One Hour

HWT-40

HWT-60

HWT-80

HWT-120

CAPACITY (Gallons)

40

55

79

119

HEAT EXCHANGER SURFACE AREA SQ.FT.

14

14

26

26

RECOMM. FLOW RATE GPM (Boiler Water)

10

10

14

14

PRESSURE DROP FT. HD. (Heat Exchanger)

2.3

2.3

11

11

FIRST HR. RATINGS GPH 90 DEGREE RISE

188

225

295

376

CONTINUOUS FLOW GPH 90 DEGREE RISE

160

187

240

293

FIRST HR. RATINGS GPH 70 DEGREE RISE

233

277

363

460

CONTINUOUS FLOW GPH 70 DEGREE RISE

205

239

308

377

BOILER SIZE BTU'S REQUIRED

120,000

140,000

180,000

220,000

PERFORMANCE RATINGS

NOTE: ABOVE RATINGS BASED ON BOILER MAINTAINING TEMPERATURE OF 180 DEGREES FAHRENHEIT.