Detailed information for ADV mode of ADV / Installer DIP switch

The SC-9 control has many features and some of these features are rarely used. These features are accessed and their settings changed
when the Adv / Installer DIP switch is in the Adv position. As a reference, listed below is the list of all the features accessed with the DIP
switch in Adv position. These are listed in sequential order as accessed in the SC-9 control.

STEP 1:

Set Adv / Installer DIP switch in Adv position.

STEP 2:

Press Mode button once.

STEP 3:

Press Item button repeatedly through the steps in sequence listed below.

Display

Description

Default

Setting

New

Setting

Room Occupied - The desired room air temperature during the occupied period.

This item is only available if the External Input/Stand Alone DIP switch is set to
Stand Alone.
Range Available: 35˚ to 100˚F (2˚ to 38˚C)

70˚F

(21˚C)

Room Unoccupied - The desired room air temperature during the unoccupied period.

This item is only available if the External Input/Stand Alone DIP switch is set to
Stand Alone.
Range Available: 35˚ to 100˚F (2˚ to 38˚C)

65˚F

(18.5˚C)

Boost - The amount of morning boost.

This item is only available if the External Input/Stand Alone DIP switch is set to
Stand Alone.
Range Available: OFF, 0:20 to 8:00 hr (5 minute increment)

OFF

Mode - Selects the staging mode of operation.

Keep on 1

SPACE HEATING WITH DHW WITH SETPOINT CONTROL