Detailed information for ADV mode of ADV / Installer DIP switch
The SC-9 control has many features and some of these features are rarely used. These features are accessed and their settings changed
when the Adv / Installer DIP switch is in the Adv position. As a reference, listed below is the list of all the features accessed with the DIP
switch in Adv position. These are listed in sequential order as accessed in the SC-9 control.
STEP 1:
Set Adv / Installer DIP switch in Adv position.
STEP 2:
Press Mode button once.
STEP 3:
Press Item button repeatedly through the steps in sequence listed below.
Display
Description
Default
Setting
New
Setting
Room Occupied - The desired room air temperature during the occupied period.
This item is only available if the External Input/Stand Alone DIP switch is set to
Stand Alone.
Range Available: 35˚ to 100˚F (2˚ to 38˚C)
70˚F
(21˚C)
Room Unoccupied - The desired room air temperature during the unoccupied period.
This item is only available if the External Input/Stand Alone DIP switch is set to
Stand Alone.
Range Available: 35˚ to 100˚F (2˚ to 38˚C)
65˚F
(18.5˚C)
Boost - The amount of morning boost.
This item is only available if the External Input/Stand Alone DIP switch is set to
Stand Alone.
Range Available: OFF, 0:20 to 8:00 hr (5 minute increment)
OFF
Mode - Selects the staging mode of operation.
Keep on 1
SPACE HEATING WITH DHW WITH SETPOINT CONTROL