D.

SPACE HEATING WITH DHW WITH SETPOINT CONTROL

General

The DIP switch settings on the control are very important and

should be set to the appropriate settings prior to making any

adjustments to the control through the User Interface. The DIP

switch settings change the items that are available to be viewed

and / or adjusted in the User Interface.

If a DIP switch is changed while the control is powered up, the

control responds to the change in setting by returning the display

to the VIEW menu.

With the exception of Adv / Installer, Rotate / OFF and

Fixed Last / OFF DIP switches, the DIP switch settings are the

same as in Section A “Space Heating with Outdoor Reset”.

DIP SWITCH SETTINGS:

CONTROL SET UP

STEP 1:

Set Advanced / Installer, Rotate / OFF and Fixed Last / OFF DIP switches as follows.

Advanced / Installer

The Adv / Installer DIP switch selects the access level of the control. In the

Installer access level, a limited number of items may be viewed and / or

adjusted. In the Advanced access level, all items may be viewed and / or

adjusted.

Set to Adv

Rotate / Off

The Rotate / Off DIP switch selects whether or not the control is to provide

Equal Run Time Rotation of the boiler stages. If the switch is set to Rotate,

the stages will be rotated accordingly. If the switch is set to Off, the firing

sequence is fixed starting with the lowest stage to the highest stage.

Set to Rotate

Fixed Last / Off

The Fixed Last / Off DIP switch selects whether or not the last boiler is to be

included in the rotation sequence. If the DIP switch is set to Fixed Last, the

last boiler is always the last to fire. This DIP switch is only active when the

Rotate/Off DIP switch is set to Rotate.

Must be set to fix last.