Space heating with dhw with setpoint control – Slant/Fin SC-9 User Manual
Page 20

20
D.
SPACE HEATING WITH DHW WITH SETPOINT CONTROL
General
The DIP switch settings on the control are very important and
should be set to the appropriate settings prior to making any
adjustments to the control through the User Interface. The DIP
switch settings change the items that are available to be viewed
and / or adjusted in the User Interface.
If a DIP switch is changed while the control is powered up, the
control responds to the change in setting by returning the display
to the VIEW menu.
With the exception of Adv / Installer, Rotate / OFF and
Fixed Last / OFF DIP switches, the DIP switch settings are the
same as in Section A “Space Heating with Outdoor Reset”.
DIP SWITCH SETTINGS:
CONTROL SET UP
STEP 1:
Set Advanced / Installer, Rotate / OFF and Fixed Last / OFF DIP switches as follows.
Advanced / Installer
The Adv / Installer DIP switch selects the access level of the control. In the
Installer access level, a limited number of items may be viewed and / or
adjusted. In the Advanced access level, all items may be viewed and / or
adjusted.
Set to Adv
Rotate / Off
The Rotate / Off DIP switch selects whether or not the control is to provide
Equal Run Time Rotation of the boiler stages. If the switch is set to Rotate,
the stages will be rotated accordingly. If the switch is set to Off, the firing
sequence is fixed starting with the lowest stage to the highest stage.
Set to Rotate
Fixed Last / Off
The Fixed Last / Off DIP switch selects whether or not the last boiler is to be
included in the rotation sequence. If the DIP switch is set to Fixed Last, the
last boiler is always the last to fire. This DIP switch is only active when the
Rotate/Off DIP switch is set to Rotate.
Must be set to fix last.