SC-9 Controller

19

C.

SPACE HEATING WITH DHW WITH OUTDOOR RESET

General

The DIP switch settings on the control are very important and

should be set to the appropriate settings prior to making any

adjustments to the control through the User Interface. The DIP

switch settings change the items that are available to be viewed

and / or adjusted in the User Interface.

If a DIP switch is changed while the control is powered up, the

control responds to the change in setting by returning the display

to the VIEW menu.

With the exception of Rotate / OFF and Fixed Last / OFF DIP

switch. The DIP switch settings are the same as in System type A

“Space Heating Only with Outdoor Reset”.

DIP SWITCH SETTINGS:

CONTROL SET UP

STEP 1:

Set Rotate / OFF and Fixed Last / OFF DIP switches as follows.

Rotate / Off

The Rotate / Off DIP switch selects whether or not the control is to provide

Equal Run Time Rotation of the boiler stages. If the switch is set to Rotate,

the stages will be rotated accordingly. If the switch is set to Off, the firing

sequence is fixed starting with the lowest stage to the highest stage.

Set to rotate

Fixed Last / Off

The Fixed Last / Off DIP switch selects whether or not the last boiler is to be

included in the rotation sequence. If the DIP switch is set to Fixed Last, the

last boiler is always the last to fire. This DIP switch is only active when the

Rotate/Off DIP switch is set to Rotate.

Must be set to fixed last.

STEP 2:

Program the control following programming steps in Section A, page 13, “Space Heating
with Outdoor Reset”.

When the WWSD (Warm Weather Shut Down) temperature is reached the operation of

DHW is still active. Control of the DHW modules during a demand for DHW by-passes the

SC-9 Control.