Boiler 2 - Selects whether or not module 2 is operational - Au (auto) or OFF
DO NOT CHANGE
Press the Menu button until ADJUST is visible on the top line of display. Press the
Item button until BOIL to the left of, and above Au and 2 is below it. Use the up and down
arrow buttons to change setting. However, the setting of Au should be retained, do not
change to OFF.
Au
Boiler 3 - Selects whether or not module 3 is operational - Au (auto) or OFF
If you do not have 3 or more boiler modules
Press the Menu button until ADJUST is visible on the top line of the display. Press the
Item button until BOIL to the left of, and above Au and 3 is below it. Use the up and down
arrow buttons to change to OFF.
Au
Boiler 4 - Selects whether or not module 4 is operational - Au (auto) or OFF
If you do not have 4 or more boiler modules
Press the Menu button until ADJUST is visible on the top line of the display. Press the
Item button until BOIL to the left of, and above Au and 4 is below it. Use the up and down
arrow buttons to change to OFF.
Au
Boiler 5 - Selects whether or not module 5 is operational - Au (auto) or OFF
If you do not have 5 or more boiler modules
Press the Menu button until ADJUST is visible on the top line of the display. Press the
Item button until BOIL to the left of, and above Au and 5 is below it. Use the up and down
arrow buttons to change to OFF.
Au
Boiler 6 - Selects whether or not module 6 is operational - Au (auto) or OFF
If you do not have 6 or more boiler modules
Press the Menu button until ADJUST is visible on the top line of the display. Press the
Item button until BOIL to the left of, and above Au and 6 is below it. Use the up and down
arrow buttons to change to OFF.
Au
Boiler 7 - Selects whether or not module 7 is operational - Au (auto) or OFF
If you do not have 7 or more boiler modules
Press the Menu button until ADJUST is visible on the top line of the display. Press the
Item button until BOIL to the left of, and above Au and 7 is below it. Use the up and down
arrow buttons to change to OFF.
Au
Boiler 8 - Selects whether or not module 8 is operational - Au (auto) or OFF
If you do not have 8 or more boiler modules
Press the Menu button until ADJUST is visible on the top line of the display. Press the
Item button until BOIL to the left of, and above Au and 8 is below it. Use the up and down
arrow buttons to change to OFF.
Au
Boiler 9 - Selects whether or not module 9 is operational - Au (auto) or OFF
If you do not have 9 or more boiler modules
Press the Menu button until ADJUST is visible on the top line of the display. Press the
Item button until BOIL to the left of, and above Au and 9 is below it. Use the up and down
arrow buttons to change to OFF.
Au
OUT
DSGN
Outdoor design - The design outdoor temperature used in the heat loss calculations for
the heating system.
Press the Menu button until ADJUST is visible on the top line of the display. Press the
Item button until OUT and DSGN appear. Use the up and down arrow buttons to change
to the desired setting.
Range Available: -60˚ to 45˚F (-51˚ to 7˚C)
10˚F
(-12˚C)
Display
Description
Default
Setting
New
Setting
SPACE HEATING ONLY WITH OUTDOOR RESET