Space heating only with outdoor reset – Slant/Fin SC-9 User Manual
Page 13

SC-9 Controller
13
General
The DIP switch settings on the control are very important and
should be set to the appropriate settings prior to making any
adjustments to the control through the User Interface. The DIP
switch settings change the items that are available to be viewed
and / or adjusted in the User Interface.
If a DIP switch is changed while the control is powered up, the
control responds to the change in setting by returning the display
to the VIEW menu.
DIP SWITCH SETTINGS:
A.
SPACE HEATING ONLY WITH OUTDOOR RESET
CONTROL SET UP
External Input / Stand Alone
The External Input / Stand Alone DIP switch selects whether a
Slant/Fin Outdoor Sensor 339070 or an external 0-10 V (dc) input
signal is to be connected to the Com - and the Out + terminals
(1 and 4).
Set to Stand Alone
Advanced / Installer
The Adv / Installer DIP switch selects the access level of the
control. In the Installer access level, a limited number of items
may be viewed and / or adjusted. In the Advanced access level,
all items may be viewed and / or adjusted.
Set to Installer
Alarm / Combustion Air
The Alarm/Combustion Air DIP switch selects whether a
combustion air damper or alarm device is to be connected to the
C.A. / Alarm terminals (12 and 13).
Set to proper position. Ignore if neither is
present.