SC-9 Controller

13

General

The DIP switch settings on the control are very important and

should be set to the appropriate settings prior to making any

adjustments to the control through the User Interface. The DIP

switch settings change the items that are available to be viewed

and / or adjusted in the User Interface.

If a DIP switch is changed while the control is powered up, the

control responds to the change in setting by returning the display

to the VIEW menu.

DIP SWITCH SETTINGS:

A.

SPACE HEATING ONLY WITH OUTDOOR RESET

CONTROL SET UP

External Input / Stand Alone

The External Input / Stand Alone DIP switch selects whether a

Slant/Fin Outdoor Sensor 339070 or an external 0-10 V (dc) input

signal is to be connected to the Com - and the Out + terminals

(1 and 4).

Set to Stand Alone

Advanced / Installer

The Adv / Installer DIP switch selects the access level of the

control. In the Installer access level, a limited number of items

may be viewed and / or adjusted. In the Advanced access level,

all items may be viewed and / or adjusted.

Set to Installer

Alarm / Combustion Air

The Alarm/Combustion Air DIP switch selects whether a

combustion air damper or alarm device is to be connected to the

C.A. / Alarm terminals (12 and 13).

Set to proper position. Ignore if neither is
present.