SPACE HEATING ONLY WITH SETPOINT CONTROL

STEP 1:

With the exception of Adv / Installer DIP switch, all DIP switches should be set the same
as in Section A, page 13, - “SPACE HEATING WITH OUTDOOR RESET”.

STEP 2:

The following adjustments should be done after you have programmed Section A -
“SPACE HEATING WITH OUTDOOR RESET”.

STEP 3:

Program the following steps.

Display

Description

Default

Setting

New

Setting

X

Outdoor Design - For Setpoint Operation MUST be adjusted.

Move the Adv / Installer DIP switch to Installer. Press the Menu button until ADJUST is
visible on the top line of the display. Press the Item button until OUT and DSGN appear.
Use the up and down arrow buttons to change the setting to 45˚F.
Range Available: -60˚ to 45˚F (-51˚ to 7˚C)

10˚F

(12˚C)

45˚F

(7˚C)

Boiler Design - The design supply water temperature used in the design of the system.
Set at least 10˚F above Boiler Minimum setting.

Move the Adv / Installer DIP switch to the Adv position temporarily. Press the Menu
button until ADJUST is visible on the top line of the display. Press the Item button until
BOIL-DSGN appears. Use the up and down arrow buttons to change to the desired
temperature. Move the Adv / Installer DIP switch back to the Installer position.
Range Available: 70˚ to 220˚F (21˚ to 104˚C)

180˚F

(82˚C)

Boiler Minimum - The Setpoint Control Temperature

Move the Adv / Installer DIP switch to the Adv position temporarily. Press the Menu
button until ADJUST is visible on the top line of the display. Press the Item button until
BOIL MIN appears. Use the up and down arrow buttons to change to the DESIRED
SETPOINT
temperature - 140˚F or more. Move the Adv / Installer DIP switch back to the
Installer position.
Range Available: OFF, 80˚ - 180˚F (OFF, 27˚ - 82˚C)

140˚F

(60˚C)

Boiler Maximum - The maximum allowed boiler target temperature. Set at least 10˚F
above Boiler Design setting
.

Move the Adv / Installer DIP switch to the Adv position temporarily. Press the Menu
button until ADJUST is visible on the top line of the display. Press the Item button until
BOIL-MAX appears. Use the up and down arrow buttons to change to the desired
temperature. Move the Adv / Installer DIP switch back to the Installer position.
Range Available: 120˚ to 225˚F or OFF (49˚ to 107˚C or OFF)

200˚F

(93.5˚C)

General

The DIP switch settings on the control are very important and

should be set to the appropriate settings prior to making any

adjustments to the control through the User Interface. The DIP

switch settings change the items that are available to be viewed

and / or adjusted in the User Interface.

If a DIP switch is changed while the control is powered up, the

control responds to the change in setting by returning the display

to the VIEW menu.

With the exception of Adv / Installer DIP switch, the DIP switch

settings are the same as in Section A “Space Heating with Outdoor

Reset”.

DIP SWITCH SETTINGS:

Please contact the Slant/Fin Technical Services Department if you need another way.
Please note that other ways may require additional relays for circulators.

Slant/Fin Technical Service 1-800-873-4346