beautypg.com

Potter Fire Alarm Systems User Manual

Page 28

background image

26

Fire Alarm Training • 8700055 • Rev F • 4/10

Where required, visual devices must be installed in the corridors of a building for visual notification. The corridor must be less

than 20 feet wide. If the corridor is wider than 20 feet then the requirements for the room spacing must be applied. The minimum

candela rating for the visual devices mounted in corridors is 15 cd. The strobes must be mounted within 15 feet of the end of the

corridor and cannot be spaced more than 100 feet apart on center. The visual devices may be mounted either on the wall or the

ceiling. They must be mounted in accordance with NFPA 72 for the proper height and placement. In addition, if there are any

interruptions in the corridor such as fire doors, partitions or changes in elevation the areas are to be viewed as separate areas.
An installer must be concerned with how visual devices, strobes in particular, are installed with respect to how many strobes are

in a field of view or room when activated. When more than two strobes are in the field of vision the strobes must be synchronized

to flash at the same time. Some people are prone to photosensitive epileptic seizures when exposed to random flashing lights and

synchronization of flashes prevent the seizure.

Room Spacing for Wall Mounted Visible Appliances (per NFPA 72)

Minimum Required Light Output (Effective Intensity, cd)

Max Room Size

ft.

One Light per Room

cd

Two Lights per Room

(Located on Opposite Walls)

Four Lights per Room

(One Light per Wall)

20 x 20

15

NA

NA

28 x 28

30

Unknown

Unknown

30 x 30

34

15

NA

40 x 40

60

30

15

45 x 45

75

Unknown

Unknown

50 x 50

94

60

30

54 x 54

110

Unknown

Unknown

60 x 60

135

95

30

70 x 70

184

95

60

80 x 80

240

135

60

90 x 90

304

185

95

100 x 100

375

240

95

110 x 110

455

240

135

120 x 120

540

305

135

130 x 130

635

375

185

NA = Not Allowable