beautypg.com

Fire alarm signals, Types of systems – Potter Fire Alarm Systems User Manual

Page 14

background image

12

Fire Alarm Training • 8700055 • Rev F • 4/10

Section 9.6.2.1.0

The “Detection” Provision

Specifies requirements for automatic detection. This section should always be reviewed, even if the building is not required to

have a fire alarm system under the general statement for that occupancy class.
There are two types of detection devices automatic and manual. The automatic detection devices include smoke detectors, heat

detectors and water flow switches. Any device that will activate the fire alarm panel or directly activate a notification appliance

without human intervention is considered automatic. Manual fire detection is generally pull stations that directly activate the fire

alarm or suppression system. Manual fire alarm systems require human intervention for the system to operate.
Section 9.6.4

The “Emergency Forces Notification” Provision

The fire alarm system may have requirements to be monitored to provide immediate notification to the fire department or fire

brigade of a fire. This section outlines the different types of monitoring stations as outlined by NFPA72.
Section 9.7 “Automatic Sprinklers and Other Extinguishing Equipment”

The occupancy class will dictate the minimum requirement for the installation of fire sprinklers, automatic extinguishing systems, fire

extinguishers and standpipes. Section 9.7 will give the appropriate NFPA Standard to follow as well as trade-offs that are allowed.
In addition to the installation requirements, NFPA 101 requires that the fire suppression equipment is inspected, tested and maintained.

Sprinkler System Supervision Includes:

Water Supply Control Valves

Alarm Line Supervision

Fire Pump Status

Water Tank, Levels and Temperature

Low and High Air Pressure on Dry Pipe Systems

Building Temperature

Water supply control valves shall be supervised to obtain a distinctive signal when in an off normal position, within 2 revolutions

of the hand wheel, or when the valve has moved one fifth from its normal position.
The switch shall not restore to a normal condition throughout the entire travel of the valve, until it is restored to a fully open position.
A Supervisory signal must be visually or audibly distinctive from both Alarm and Trouble signals.
Water flow and supervisory devices cannot be connected on the same initiating circuit so that the closing of a valve is

annunciated as a “trouble” condition.

Fire Alarm Signals

Alarm - A signal indicating an emergency that requires immediate action, such as a signal indicative of a fire.

1. Automatic water flow device

2. Manual fire alarm station (pull station)

3. Automatic fire detectors (smoke or heat detectors)
Supervisory – A signal indicating the need for action in connection with the

supervision of guard tours, the fire suppression

systems or equipment, or the maintenance features of related systems.

1. Control valve switch

2. High/low air pressure switch
3. Water tank level and temperature switches

4. Low water pressure for public water supplies

5. Low building temperature switch

6. Alarm line valve position
Trouble - A signal indicating a problem with the fire control panel or associated wiring which may render the system inoperable.

1. Loss of primary power (120VAC)

2. Loss of secondary power (battery)

3. A break in the supervised wiring to an initiating device, indicating appliance or extinguishing agent release device

Types of Systems

Conventional

Conventional fire alarm systems are comprised of initiating and notification zones. The number of initiating zones (initiating

device circuits) defines how large the system can be. The zones are generally a specific function (pull station, water flow switch,