Fire Alarm Training • 8700055 • Rev F • 4/10

DWG# 55-13

15’

20’

Double the longest distance to determine the

maximum room size.

30 Feet x 30 Feet would be the minimum

room size used.

Room Spacing for Ceiling-Mounted Visible Appliances

Maximum Room Size

Maximum Ceiling Minimum Required Light Output

Height

(Effective Density); One Light (cd)

m

ft

m

ft

   cd

6.1 x 6.1

20 x 20

3.05

10

15

9.14 x 9.14

30 x 30

3.05

10

30

12.2 x 12.2

40 x 40

3.05

10

60

15.2 x 15.2

50 x 50

3.05

10

95

6.1 x 6.1

20 x 20

6.1

20

30

9.14 x 9.14

30 x 30

6.1

20

45

12.2 x 12.2

40 x 40

6.1

20

80

15.2 x 15.2

50 x 50

6.1

20

115

6.1 x 6.1

20 x 20

9.14

30

55

9.14 x 9.14

30 x 30

9.14

30

75

12.2 x 12.2

40 x 40

9.14

30

115

15.2 x 15.2

50 x 50

9.14

30

150