Initiating devices – Potter Fire Alarm Systems User Manual
Page 16

14
Fire Alarm Training • 8700055 • Rev F • 4/10
DWG# 55-1
POS. +
POS. +
FACP CLASS A ZONE
NEG. -
NEG. -
SMOKE
DETECTORS
The Signaling Line Circuits (SLC) in addressable systems have additional devices that can isolate short circuits so the loop
will still fully operate. These types of installations are generally required in government installations, some hospitals and some
schools. These systems are more expensive to install and may require additional equipment, however there is greater redundancy
built into the system.
Initiating Devices
Smoke Detector Placement
Detector placement is critical to early warning functions. In order to provide an effective early warning of a developing fire
situation, smoke detectors should be installed in all areas of the protected premises. The location, quantity and zoning of detectors
should be engineered to provide maximum life safety.
Defining the smoke chamber
The continuous, smoke resistant perimeter boundary of a room or area to be protected between the upper surface of the floor and
the lower surface of the ceiling. The smoke barrier does not have to be a solid structure from floor to ceiling. A solid structure that
extends 18” or more from the ceiling would constitute a smoke barrier.
Open “grid” material is considered solid when:
* The openings are less than 1/4” in the least dimension
* The thickness of the material exceeds the least dimension
* The openings constitute less than 70% of the area of the perforated material
DWG# 55-2
POS. +
FACP CLASS B ZONE
NEG. -
Circuit Types
Fire alarm circuits are wired either Class A or Class B and both have advantages and disadvantages. The Class A circuit utilizes
a pair of wires to attach to all of the devices and then a pair returns back to the panel. NFPA 72 requires that a minimum distance
separates the outgoing and return wires on class A wiring. If a break occurs anywhere in the circuit, every device is still active due
to the redundant circuit paths. There are four wires, two supplying power to the front of the circuit and two supplying power from
the end of the circuit.
As described earlier, the conventional systems use the end of line resistor to monitor the status of the zones. If a wire is broken
or a device removed, the panel detects the lack of the end of line resistor and annunciates a trouble condition. Similarly most
notification appliance circuits use an end of line resistor as well. These circuits are monitored for open circuits as well as short
circuits. In addition, both circuits are monitored for ground faults or a high amount of resistance to ground potential. A ground can
impede the proper operation of a circuit.
Detectors and notification appliances must be wired to ensure supervision of the device. Removal of the detector head or
notification appliance must cause a trouble condition on the panel.
Conventional panels send a small amount of power out to the initiating devices and end-of-line resistor. The panel measures the
amount of current being consumed. If the current is in the normal or midrange the panel is normal. If the panel detects too little
current that is indicative of an open and the panel indicates a trouble condition. If the panel sees too high of a current the panel
interrupts that as a short and indicates an alarm condition. Dry contact devices such as pull stations and heat detectors put a direct
short on the initiating circuit and put the panel into alarm.
The most common installation is Class B utilizing two wires that connect to each device and an end-of-line resistor for wiring
supervision. Unlike Class A circuits, Class B circuits will not fully operate when a wire break occurs. Every device down stream
of the break will be unavailable until the wire problem is corrected. The panel will, however indicate a trouble signal.