beautypg.com

Potter Fire Alarm Systems User Manual

Page 19

background image

17

Fire Alarm Training • 8700055 • Rev F • 4/10

ANYWHERE

IN THIS AREA

900mm

(3 ft)

900mm

(3 ft)

1/2 S

S

S

1/2 S

S

= SPACE BETWEEN DETECTORS

= SMOKE DETECTOR OR HEAT DETECTOR

DWG# 55-5

DO NOT

INSTALL

WITHIN 4”

OF PEAK

Raised Floors and Suspended Ceilings

Spaces between raised floors and above suspended ceilings shall be treated as separate rooms for smoke detector spacing

purposes. Detectors installed beneath raised floors or above suspended ceilings used for environmental air, shall not be used in

lieu of providing detection within the room. NFPA 72 2007, 5.7.3.7
To minimize dust collection, smoke detectors, where installed under raised floors, detectors shall only be mounted in an

orientation in which they been listed. NFPA 72 2007, 5.7.3.2.2
Detectors shall not be installed until after the construction cleanup of all trades is complete and final.

Exception: Where required by the authority having jurisdiction for protection during construction. Detectors that have been

installed during construction and found to have a sensitivity outside the listed and marked sensitivity range shall be cleaned or

replaced in accordance with Chapter 10 at completion of construction. NFPA 72 2007, 5.7.1.11
Smoke detectors can be installed on the ceiling or wall. When installed on a ceiling, no portion of the detector may be within 4” of a sidewall.

Ceiling 4”

Wall

No portion of a detector may

ever be installed in this triangle.

This is considered “Dead Air”

When installed on a wall, no portion of the detector mey be installed within 4” of the ceiling. Some portion of the detector must

be within 4”-12” of the ceiling.

Ceiling

4”

Some portion of the

detector must be

installed in this.

12”