Carrier 19XL User Manual
Page 30

Table 3 — Protective Safety Limits and Control Settings
MONITORED PARAMETER
LIMIT
APPLICABLE COMMENTS
TEMPERATURE SENSORS
OUT OF RANGE
–40 to 245 F (–40 to 118.3 C)
Must be outside range for 2 seconds
PRESSURE TRANSDUCERS
OUT OF RANGE
0.08 to 0.98 Voltage Ratio
Must be outside range for 2 seconds.
Ratio = Input Voltage ÷ Voltage
Reference
COMPRESSOR DISCHARGE
TEMPERATURE
Ͼ
220 F (104.4 C)
Preset, alert setting configurable
MOTOR WINDING TEMPERATURE
Ͼ
220 F (104.4 C)
Preset, alert setting configurable
BEARING TEMPERATURE
Ͼ
185 F (85 C)
Preset, alert setting configurable
EVAPORATOR REFRIGERANT
TEMPERATURE
Ͻ
33 F (for water chilling) (0.6° C)
Preset, configure chilled medium for
water (Service1 table)
Ͻ
Brine Refrigerant Trippoint (set point adjustable
from 0 to 40 F [–18 to 4 C] for brine chilling)
Configure chilled medium for brine
(Service1 table). Adjust brine refrigerant
trippoint for proper cutout
TRANSDUCER VOLTAGE
Ͻ
4.5 vdc
Ͼ
5.5 vdc
Preset
CONDENSER PRESSURE — SWITCH
Ͼ
263 ± 7 psig (1813 ± 48 kPa),
reset at 180 ± 10 (1241 ± 69 kPa)
Preset
— CONTROL
Ͼ
260 psig (1793 kPa) for HCFC-22;
215 psig (1482 kPa) for HFC-134a
Preset
OIL PRESSURE — SWITCH
Cutout
Ͻ
11 psid (76 kPad) ± 1.5 psid (10.3 kPad)
Cut-in
Ͼ
16.5 psid (114 kPad) ± 4 psid (27.5 kPad)
Preset, no calibration needed
— CONTROL
Cutout
Ͻ
15 psid (103 kPad)
Alert
Ͻ
18 psid (124 kPad)
Preset
LINE VOLTAGE — HIGH
Ͼ
110% for one minute
Preset, based on transformed line volt-
age to 24 vac rated-input to the Starter
Management Module. Also monitored at
PSIO power input.
— LOW
Ͻ
90% for one minute or
р
85% for 3 seconds
— SINGLE-CYCLE
Ͻ
50% for one cycle
COMPRESSOR MOTOR LOAD
Ͼ
110% for 30 seconds
Preset
Ͻ
10% with compressor running
Preset
Ͼ
10% with compressor off
Preset
STARTER ACCELERATION TIME
(Determined by inrush current
going below 100% compressor
motor load)
Ͼ
45 seconds
For chillers with reduced voltage me-
chanical and solid-state starters
Ͼ
10 seconds
For chillers with full voltage starters
(Configured on Service1 table)
STARTER TRANSITION
Ͼ
75 seconds
Reduced voltage starters only
CONDENSER FREEZE
PROTECTION
Energizes condenser pump relay if condenser
refrigerant temperature or condenser entering
water temperature is below the configured con-
denser freeze point temperature. Deenergizes
when the temperature is 5 F (3 C) above con-
denser freeze point temperature.
CONDENSER FREEZE POINT config-
ured in Service01 table with a default
setting of 34 F (1 C).
Flow Switches (Field Supplied)
Operate water pumps with chiller off. Manually
reduce water flow and observe switch for proper
cutout. Safety shutdown occurs when cutout time
exceeds 3 seconds.
CUT-OUT
SETTING
ADJUSTMENT
SCREW
30