Carrier 19XL User Manual
Page 21

Table 2 — LID Screens
NOTES:
1. Only 12 lines of information appear on the LID screen at any given time. Press
NEXT
or PREVIOUS to highlight a point or to view points
below or above the current screen.
2. The LID may be configured in English or SI units, as required, through the LID configuration screen.
3. Data appearing in the Reference Point Names column is used for CCN operations only.
4. All options associated with ICE BUILD, Lead/Lag, CCN Occupancy Configuration, and Soft Stopping are only available on PSIO Software
Version 9 and higher.
EXAMPLE 1 — STATUS01 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press
MENU
.
2. Press STATUS (STATUS01 will be highlighted).
3. Press SELECT .
DESCRIPTION
RANGE
UNITS
REFERENCE POINT NAME
(ALARM HISTORY)
Control Mode
Reset, Off, Local, CCN
MODE
Run Status
Timeout, Recycle, Startup,
Ramping, Running, Demand, Override,
Shutdown, Abnormal, Pumpdown
STATUS
Occupied ?
No/Yes
OCC
Alarm State
Normal/Alarm
ALM
*Chiller Start/Stop
Stop/Start
CHIL
S
S
Base Demand Limit
40-100
%
DLM
*Active Demand Limit
40-100
%
DEM
LIM
Compressor Motor Load
0-999
%
CA
L
Current
0-999
%
CA
P
Amps
0-999
AMPS
CA
A
*Target Guide Vane Pos
0-100
%
GV
TRG
Actual Guide Vane Pos
0-100
%
GV
ACT
Water/Brine: Setpoint
10-120 (–12.2-48.9)
DEG F (DEG C)
SP
*
Control Point
10-120 (–12.2-48.9)
DEG F (DEG C)
LCW
STPT
Entering Chilled Water
–40-245 (–40-118)
DEG F (DEG C)
ECW
Leaving Chilled Water
–40-245 (–40-118)
DEG F (DEG C)
LCW
Entering Condenser Water
–40-245 (–40-118)
DEG F (DEG C)
ECDW
Leaving Condenser Water
–40-245 (–40-118)
DEG F (DEG C)
LCDW
Evaporator Refrig Temp
–40-245 (–40-118)
DEG F (DEG C)
ERT
Evaporator Pressure
–6.7-420 (–46-2896)
PSI (kPa)
ERP
Condenser Refrig Temp
–40-245 (–40-118)
DEG F (DEG C)
CRT
Condenser Pressure
–6.7-420 (–46-2896)
PSI (kPa)
CRP
Discharge Temperature
–40-245 (–40-118)
DEG F (DEG C)
CMPD
Bearing Temperature
–40-245 (–40-118)
DEG F (DEG C)
MTRB
Motor Winding Temp
–40-245 (–40-118)
DEG F (DEG C)
MTRW
Oil Sump Temperature
–40-245 (–40-118)
DEG F (DEG C)
OILT
Oil Pressure Transducer
–6.7-420 (–46-2896)
PSI (kPa)
OILP
Oil Pressure
–6.7-420 (–46-2896)
PSID (kPad)
OILPD
Line Voltage:
Percent
0-999
%
V
P
Actual
0-9999
VOLTS
V
A
*Remote Contacts Input
Off/On
REMCON
Total Compressor Starts
0-65535
c
starts
Starts in 12 Hours
0-8
STARTS
Compressor Ontime
0-500000.0
HOURS
c
hrs
*Service Ontime
0-32767
HOURS
S
HRS
*Compressor Motor kW
0-9999
kW
CKW
NOTE: All values are variables available for read operation to a CCN. Descriptions shown with (*) support write operations for BEST programming
language, data transfer, and overriding.
21