Dip switches, Input power, Communication wiring – Keri Systems MR51e User Manual

Page 3: Reader wiring

background image

Mercury Security © 2013

MR51e

DOC 10107-0035

REV 1.05

Page 3

3. DIP Switches:

The addressing mode used is determined by the DIP switch setting on the MR51e:

4

3

2

1

Addressing Mode Meaning

OFF OFF OFF OFF MSC-Specific DHCP (original method)

OFF OFF OFF ON

Public DHCP

OFF OFF ON

OFF Static IP

OFF OFF ON

ON

Programming Mode for Static IP Address Assignment

ON

ON

ON

ON

MSC-Specific DHCP (original method)

Notes:

Public DHCP and Static IP Addressing Modes are available with MR51e firmware

revisions 1_4_2 and later

 All other DIP switch settings are reserved for future use
 Press S2 to reset board after DIP switch is changed for new address mode

4. Input Power:

The MR51e is powered by one of two ways (jumper selected):

Power is supplied via the Ethernet connection using PoE, fully compliant to IEEE 802.3af

Or local 12 Vdc power supply, TB5-3 (VIN), TB5-4 (GND).

5. Communication Wiring:

Communication between the EP controller and the MR51e is Ethernet. (10Base-T/100Base-TX)

6. Reader Wiring:

The first reader port supports Wiegand, magnetic stripe, and 2-wire RS-485 electrical interfaces. The
second reader port supports Wiegand and magnetic stripe electrical interfaces. Power to the first reader
is 12 Vdc and is current limited to 150 mA. The second reader may be powered from the auxiliary power
output on TB5-1 and TB5-2. Readers that require different voltage or have high current requirements
should be powered separately. Refer to the reader manufacture specifications for cabling requirements.
In the 2-wire LED mode, the Buzzer output is used to drive the second LED. Reader port configuration
is set via the host software.

When powering any remote device(s) by the MR51e, care must be taken not to exceed the maximum
current available. Cable gauge must also be evaluated. See specifications section for details.

MR

-1

0/

20 R

EA

DE

R

ADDRESS 0

MR-DT

RS-485 MODE

9600 BAUD

TB

3

TB

3

FIRST READER PORT
DATA1/DATA0 OR CLOCK/DATA

FIRST READER PORT
2-WIRE RS-485

WHT (3)

BLK (6)

GRN (2)

ORG (5)

BRN (4)

RED (1)

CLK/D1

GND

DAT/D0

LED
BZR

VO

12Vdc (RED) (1)

TR+ (BLUE) (3)

GROUND (BLACK) (2)

TR- (GRAY) (4)

DAT/D0

CLK/D1

GND

VO