beautypg.com

Keri Systems SB-293 User Manual

Page 12

background image

Technical Reference Manual – PXL-250 and SB-293

Keri Systems, Inc.

Page 12

P/N: 01836-004

Revision 5.5

Network Communications

an RS-232 serial port that automatically configures itself to communicate directly
to a PC or communicate to a PC via modem

an RS-485 network communication port capable of linking up to 128 controllers
on a single network up to 4,000 feet long (or up to 16,000 feet under specific
conditions – refer to Appendix 3: PXL-250 Network Wiring Application Note)

Automatic Network Configuration

automatic configuration of earth ground to one point to support network
communications

Access Control Database Capacity

transaction buffers capable of storing up to 3,640 events per controller

a database capacity of up to 10,920 unique cardholders per controller, OR

with optional RAM expansion, up to 65,535 unique cardholders per controller

Support for the Following Reader Technologies

Keri Systems Proximity

Wiegand Compatible (26-bit)

– Bar Code
– Biometrics
– Keypad
– Magnetic Stripe
– Other Proximity

NOTE: Wiegand readers must send data according to the Security Industry
Association's Wiegand Reader Interface Standard (document number AC-01D-96).
Keri Systems, Inc. cannot guarantee the performance or reliability of Wiegand readers
that do not meet these guidelines.

The optional LCD-1 Alpha/Numeric Plug-In Display adds the following feature.

access to built-in system diagnostics to aid in troubleshooting (highly
recommended)

This manual is related to the following products: