FloAire DDC User Manual
Page 8

8
AV: 4: Effective Heating Setpoint. This is the effective heating setpoint, after the inclusion of
internal logic to prevent rapid ramp-up/down of the value.
Properties
- Fixed readout. Non-editable
- BACnet Reference: eht_stpt
- Modbus Register: 40017
- N2 Register: 9
- Lonworks ID: nvoEffHeatStp
- Units of degrees Fahrenheit (can be changed in software)
- Has a maximum rise of 5.0 Degrees per 1 minute from AV:3
- Has a maximum fall of 5.0 Degrees per 1 minute from AV:3
AV: 5: Heating Intake Air Activation Setpoint. This variable is used to activate the call for heat. If
the Intake Air Temperature Sensor Value falls below this value, the call for heat output will be
activated.
Properties
- Editable, precision to the tenth of a degree.
- BACnet Reference: ht_iat_stpt
- Modbus Register: 40025
- N2 Register: 13
- Lonworks ID: nviHeatIntakeStp
- Units of degrees Fahrenheit (can be changed in software)
- Range: 40.0 to 90.0
- Default: 45.0
AV: 6: Cooling Intake Air Setpoint. This variable is used to activate the call for stage 1 cooling.
If the Intake Air Temperature Sensor Value rises above this value, the stage 1 cooling output will
be activated.
Properties
- Editable, precision to the tenth of a degree.
- BACnet Reference: cl_iat_stpt
- Modbus Register: 40003
- N2 Register: 2
- Lonworks ID: nviCoolIntakeStp
- Units of degrees Fahrenheit (can be changed in software)
- Range: 60.0 to 120.0
- Default: 85.0
AV: 7: Effective Cooling Setpoint. This is the effective cooling setpoint, after the inclusion of
internal logic to prevent rapid ramp-up/down of the value.
Properties
- Fixed readout. Non-editable
- BACnet Reference: ecl_stpt
- Modbus Register: 40013
- N2 Register: 7
- Lonworks ID: nvoEffCoolStp
- Units of degrees Fahrenheit (can be changed in software)
- Has a maximum rise of 5.0 Degrees per 5 minutes from AV:6
- Has a maximum fall of 3.0 Degrees per 5 minutes from AV:6