FloAire DDC User Manual
Page 15

15
BV: 11: 2nd Stage Cooling Command. This is the command used to activate the stage 2 cooling
output from the controller.
Properties
- Fixed readout. Status only.
- Network Reference: s2_clg_cmd
- Modbus Register: 10001
- N2 Register: 1
- Lonworks ID: nvoCoolTwoCmd
- Activates from either BV: 10 or when the call for second stage cooling logic is satisfied
using AV: 2, AV: 7, and AV: 8
BV: 12: Heat On Command. This is the command used to activate the call for heat relay.
Properties
- Fixed readout. Status only.
- Network Reference: ht_on_cmd
- Modbus Register: 10004
- N2 Register: 4
- Lonworks ID: nvoHeatOnCmd
- Activates when a call for heat is determined from comparison of AV: 2 to AV: 5
BV: 13: Clogged Filter Status. This is the status of the clogged filter input to the controller. A
value displayed here is only relevant if the clogged filter option was ordered with the unit.
Properties
- Fixed readout. Status only.
- Network Reference: fltr_sts
- Modbus Register: 10003
- N2 Register: 3
- Lonworks ID: nvoClogFltrSts
- Activates when the clogged filter input is On. An On state is the normal run condition.
An Off state indicates clogged filter. A clogged filter alarm will sound (see alarm section).
BV: 14: Smoke Detector Status. This is the status of the smoke detector input to the controller.
A value displayed here is only relevant if the smoke detector option was ordered with the unit.
Properties
- Fixed readout. Status only.
- Network Reference: smk_sts
- Modbus Register: 10009
- N2 Register: 9
- Lonworks ID: nvoSmokDtctSts
- Activates when the smoke detector input is On. An On state is the alarm state
condition. A Smoke alarm will sound and shut down the unit (see alarm section).
BV: 15: Emergency Alarm. This is the network input for an emergency alarm. If the network
value of this input is changed to On, the unit will shut down.
Properties
- On/Off Switch
- Network Reference: emerg_alm_in
- Modbus Register: 4
- N2 Register: 4
- Lonworks ID: nviEmerAlarmOn