FloAire DDC User Manual
Page 18
18
-
Network Reference: oad_rntm
-
Modbus Register: 10023
-
N2 Register: 23
-
Lonworks ID: nvoOadRntmAlm
-
Activates if BV: 7 has been in the On state for 10000 hours.
BV: 42 SAT_HI: High Supply Air Temperature.
-
Network Reference: sat_hi
-
Modbus Register: 10024
-
N2 Register: 24
-
Lonworks ID: nvoSATHiAlm
-
Activates if AV: 9, the Discharge Air Temperature, is greater than 160 Degrees for 10:00
minutes, and the unit has proper airflow.
BV: 43 SAT_LO: Low Supply Air Temperature.
-
Network Reference: sat_lo
-
Modbus Register: 10025
-
N2 Register: 25
-
Lonworks ID: nvoSATLoAlm
-
Activates if AV: 9, the Discharge Air Temperature, is less than 35 Degrees for 10:00 minutes,
and the unit has proper airflow.
BV: 44 SF_FAIL: Supply Fan Failure.
-
Network Reference: sf_fail
-
Modbus Register: 10026
-
N2 Register: 26
-
Lonworks ID: nvoSfFailAlm
-
Activates if BV: 3, the Supply Fan Command, is Off, however BV: 4, the Supply Fan Status, is
On. There is a 30 second feedback delay.
BV: 45 SF_HAND: Supply Fan In Hand.
-
Network Reference: sf_hand
-
Modbus Register: 10027
-
N2 Register: 27
-
Lonworks ID: nvoSFHandAlm
-
Activates if BV: 3, the Supply Fan Command, is On, however BV: 4, the Supply Fan Status, is
Off. There is a 30 second feedback delay.
BV: 46 SF_RNTM: Supply Fan Runtime Expired.
-
Network Reference: sf_rntm
-
Modbus Register: 10028
-
N2 Register: 28
-
Lonworks ID: nvoSfRntmAlm
-
Activates if BV: 4 has been in the On state for 10000 hours.
BV: 47 SMOKE: Smoke Detector Alarm.
-
Network Reference: smoke
-
Modbus Register: 10029
-
N2 Register: 29
-
Lonworks ID: nvoSmokeAlm
-
Activates if BV: 14, the Smoke Detector Status, is in the On state. There is no delay.
-
This alarm is a shutdown alarm.