Troubleshooting Flowcharts









































Blower runs

but there is

no heat

Is Outside

temperature higher

than temp selector?

No heat required

YES

Is LED on FSC

energized?

Check wiring to

combination

valve

NO

YES

Is there 24V at

amplifier

terminal #11

Power vent not

functioning, high

limit activation,

or BVSS trip

Is there 24V at

amplifier

terminal #9?

Check wiring

from 24V

transformer

Refer to Maxitrol

Literature

NO

YES

YES

NO

NO

Burner lights but heater

stays in High Fire

Is temperature rise

requirement low?

System

Operating

Properly

With wires 3 & 4 removed

from the Maxitrol Amplifier,

is there 8K to 12K Ohms

between the wires?

If above 12K

Ohms, check

for open

circuit.

Is Plunger in the

Modulating Valve jammed?

Inspect and clean. It

should operate freely in the

sleeve.

Foreign object holding

valve open. Remove

bottom plate and inspect

valve and seat. Clean or

replace valve.

NO

YES

YES

NO

YES

Is Freeze-Stat

open?

Adjust or

Replace

Is end switch on

Motorized

Damper closed?

Adjust or

Replace
actuator

YES

YES

NO

Nothing

Happens

Is Overload

tripped on

starter?

Reset & measure FLA

of motor. Is it higher

than rating?

Adjust

or

change

Pulley

NO

NO

YES

Burner lights but

heater stays in

Low Fire

Is temperature rise

requirement low?

System operating

properly

With wires 3 & 4

removed from the

Maxitrol Amplifier, is

there 8K to 12K

Ohms between the

wires?

If below 8K Ohms,

check for short circuit.

Remove Terminal #3

from the Maxitrol

Amplifier. Does the

heater go into High Fire?

YES

NO

YES

NO

YES

Refer to Maxitrol

Amplifier literature

NO

Refer to Maxitrol Valve

Literature