Remote panel troubleshooting chart – FloAire Indirect Fired Heater User Manual
Page 23

23
Remote Panel Troubleshooting Chart
Light Indication
Condition
Possible Cause
No Lights
Power not available to Remote Panel
Bad voltage to unit
Main disconnect in “OFF” Position
Circuit breaker tripped
Bad main transformer
POWER Light Only
Proper unit Off Operation
No problem
No power to motor starter
Blower On/Blower Off Switch in “Blower
Off” Position
Improper damper function
Low Temperature Thermostat Timed
Out (Option)
Improper Airflow
Insufficient Airflow
Bad airflow switch
Problem with air probes
Problem with airflow tubing
Broken Belt
POWER Light and
BLOWER ON Light
Proper Ventilation Operation
No Problem
No Power to Flame Safety Controller
Heat/Vent Switch in “Vent” Position
Gas Pressure Switch Tripped (option)
High Temperature Limit Thermostat
Tripped
CLOGGED FILTER Light On
(Optional)
Filters Clogged
Filters Dirty or Need Replacement
LOW TEMP Light On
(Optional)
Freeze-stat has shut blower down
Discharge Temperature Too Cold
Heating System is not Functioning
POWER Light and
BLOWER ON Light and
HEAT ON Light
Proper Heating Operation
No Problem