DIAGNOSTIC CHARTS (CONT.)

Outdoor coil clean?

Clean coil. Problem

persists?

Indoor filter clean?

Clean filter. Problem

persists?

Check indoor fan

motor

Replace indoor fan

motor.

Normal suction,

high head?

High head, high

suction?

High head, low

suction?

Yes

Yes

Yes

No

No

No

Problem solved

Problem solved

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Check application
limits.

Non condensables
in sys. Pump down
and recharge unit

See note below *

* Restriction in system. Check capillary tube and check for damage to liquid line between indoor and

outdoor units.

Connect low side gauge
at suction service valve.
Measure discharge temp.*

Unit is overcharged.
Reclaim charge and
weigh in correct charge

Outdoor coil clean?

Clean coil. Problem

persists?

Indoor filter clean?

Clean filter. Problem

persists?

Check indoor fan

motor

Replace indoor fan

motor.

Normal suction,

high head?

High head, high

suction?

High head, low

suction?

Yes

Yes

Yes

No

No

No

Problem solved

Problem solved

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Check application
limits.

Non condensables
in sys. Pump down
and recharge unit

See note below *

* Restriction in system. Check capillary tube and check for damage to liquid line between indoor and

outdoor units.

Connect low side gauge
at suction service valve.
Measure discharge temp.*

Unit is overcharged.
Reclaim charge and
weigh in correct charge

A09368

Fig. 36 – Unit Not Running Optimally

Visually check outdoor

Unit for ice blockage.

**

Check reversing valve.

Go to flow chart 12

No

Yes

Yes

Check defrost sensor. Ok?

Go to flow chart 2

No

Replace sensor

Check application limits.

Ok?

* To supplement flow chart 9
** Check for blockage on outdoor coil and drain pan. Are the holes in drain pans blocked?

No

Beyond operating range

Yes

Yes

Check ambient conditions.

Prime icing?

Explain to customer

Visually check outdoor

Unit for ice blockage.

**

Check reversing valve.

Go to flow chart 12

No

Yes

Yes

Check defrost sensor. Ok?

Go to flow chart 2

No

Replace sensor

Check application limits.

Ok?

* To supplement flow chart 9
** Check for blockage on outdoor coil and drain pan. Are the holes in drain pans blocked?

No

Beyond operating range

Yes

Yes

Check ambient conditions.

Prime icing?

Explain to customer

A09369

Fig. 37 – Unit Not Running Optimally (HP in Heating*)