DIAGNOSTIC CHARTS (CONT.)

Is unit running in outdoor
ambient higher than
110 °F?

Beyond operating range

Outdoor coil clean?

Clean coil.

Problem persists?

Problem solved

Check outdoor coil
temperature thermistor .
Chart 4, ok?

Check motor for open
or short. Ok?

Check output on outdoor
board. Ok?

Replace outdoor board

Replace thermistor .

Problem persists

Problem solved

Replace outdoor motor

Yes

No

No

Yes

No

No

No

Yes

No

Yes

Yes

Yes

No

Is unit running in outdoor
ambient higher than
110 °F?

Beyond operating range

Outdoor coil clean?

Clean coil.

Problem persists?

Problem solved

Check outdoor coil
temperature thermistor .
Chart 4, ok?

Check motor for open
or short. Ok?

Check output on outdoor
board. Ok?

Replace outdoor board

Replace thermistor .

Problem persists

Problem solved

Replace outdoor motor

Yes

No

No

Yes

No

No

No

Yes

No

Yes

Yes

Yes

No

A09364

Fig. 32 – High Condensing Temperature

Is unit running in outdoor
ambient higher than
110 °F?

Beyond operating range

Outdoor coil clean?

Clean coil.

Problem persists?

Problem solved

Check connections from
OD board. Loose, corroded,
or high resistance?

Check output on
outdoor board. Ok?

Connect low side gauge at
suction service valve.
Measure discharge temp.*

Check amp draw to
compressor? Values within
range?

Replace outdoor board

Replace compressor

Clean/repair connection

Problem persists?

Problem solved

Replace outdoor board

High head, high suction?

High head, low suction?

Unit is overcharged.

Reclaim charge and weigh

in correct charge.

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

No

No

No

Yes

Yes

No

No

Yes

Yes

Restriction in refrigeration

circuit.

Yes

Outdoor motor ok?

No

Replace motor

*Measure discharge temperature at the sensor on the discharge

tube. See Appendix A5

Is unit running in outdoor
ambient higher than
110 °F?

Beyond operating range

Outdoor coil clean?

Clean coil.

Problem persists?

Problem solved

Check connections from
OD board. Loose, corroded,
or high resistance?

Check output on
outdoor board. Ok?

Connect low side gauge at
suction service valve.
Measure discharge temp.*

Check amp draw to
compressor? Values within
range?

Replace outdoor board

Replace compressor

Clean/repair connection

Problem persists?

Problem solved

Replace outdoor board

High head, high suction?

High head, low suction?

Unit is overcharged.

Reclaim charge and weigh

in correct charge.

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

No

No

No

Yes

Yes

No

No

Yes

Yes

Restriction in refrigeration

circuit.

Yes

Outdoor motor ok?

No

Replace motor

*Measure discharge temperature at the sensor on the discharge

tube. See Appendix A5

A09365

Fig. 33 – Compressor Overcurrent Protection