9

Furnace is shipped from factory in upflow configuration. Pressure tube and drain tube routing MUST match the diagrams below.

Tube location when used in DOWNFLOW application

Tube location when used on

HORIZONTAL - RIGHT application

PLUG

CAP

COLLECTOR BOX DRAIN TUBE

(BLUE & WHITE STRIPED)

COLLECTOR BOX TUBE

(PINK)

COLLECTOR BOX DRAIN TUBE

(BLUE)

INDUCER HOUSING DRAIN TUBE

(VIOLET)

COLLECTOR BOX TUBE

(PINK)

COLLECTOR BOX DRAIN

TUBE

(BLUE & WHITE STRIPED)

COLLECTOR BOX DRAIN TUBE

(BLUE)

INDUCER HOUSING (MOLDED) DRAIN TUBE

(BEHIND COLLECTOR BOX DRAIN TUBE)

FIELD-INSTALLED

FACTORY-SUPPLIED DRAIN TUBE

COUPLING (LEFT DRAIN OPTION)

FIELD-INSTALLED FACTORY-SUPPLIED

DRAIN TUBE

FIELD-INSTALLED

FACTORY-SUPPLIED 1/2-IN.

CPVC STREET ELBOWS (2)

FOR LEFT DRAIN OPTION

COLLECTOR BOX TUBE

(GREEN)

CONDENSATE TRAP

CAP

Condensate Trap; Factory Installed

in Blower Shelf

CONDENSATE TRAP

COLLECTOR BOX TUBE (GREEN)

Condensate Trap on LEFT

Side Optional

CAP

COLLECTOR BOX

DRAIN TUBE (BLUE)

PLUGGED END

COLLECTOR BOX DRAIN TUBE

(BLUE & WHITE STRIPED)

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX

EXTENSION TUBE

CONDENSATE TRAP

INDUCER HOUSING DRAIN TUBE (VIOLET)

COLLECTOR BOX

EXTENSION TUBE

Condensate Trap on

RIGHT Side

PLUG

CAP

COLLECTOR BOX DRAIN TUBE

(BLUE & WHITE STRIPED)

CONDENSATE TRAP

COLLECTOR BOX

EXTENSION TUBE

COLLECTOR BOX

TUBE (GREEN)

INDUCER HOUSING

DRAIN TUBE

(VIOLET)

COLLECTOR BOX TUBE (PINK)

RELOCATE TUBE BETWEEN BLOWER

SHELF AND INDUCER HOUSING FOR

060 AND 080 HEATING INPUT

FURNACES

CAP

PLUG

COLLECTOR BOX DRAIN TUBE

(BLUE)

COLLECTOR BOX EXTENSION TUBE

COLLECTOR BOX TUBE (PINK)

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX DRAIN TUBE

(BLUE AND WHITE STRIPED)

INDUCER HOUSING DRAIN TUBE (VIOLET)

CONDENSATE TRAP

Condensate Trap on

LEFT Side

COLLECTOR BOX

DRAIN TUBE (BLUE)

PLUG

Tube location when used in UPFLOW application

Tube location when used on

HORIZONTAL - LEFT application

PLUG

COLLECTOR BOX

EXTENSION TUBE

DRAIN TUBE

COUPLING

COLLECTOR BOX EXTENSION DRAIN TUBE

(Blower access panel removed)

FIELD-INSTALLED

FACTORY- SUPPLIED

DRAIN TUBE COUPLING

(RIGHT DRAIN OPTION)

BURNER ENCLOSURE

PRESSURE REFERENCE

TUBE ASSEMBLY

BURNER ENCLOSURE

PRESSURE REFERENCE

TUBE ASSEMBLY

BURNER ENCLOSURE

PRESSURE REFERENCE

TUBE ASSEMBLY

BURNER ENCLOSURE

PRESSURE REFERENCE

TUBE ASSEMBLY

BURNER ENCLOSURE PRESSURE

REFERENCE TUBE ASSEMBLY

TUBE ROUTING

AUXILIARY "J" BOX RELOCATED HERE

NOTE:

326476-201 REV. B
(lit-bottom)

1. All tubing must be connected securely and routed to avoid kinks and traps.

2. Pressure tubing must always slope away from pressure switch to collector box connection as shown.

3. HORIZONTAL-LEFT installations require the collector box pressure tube to be relocated between the inducer housing and the blower shelf to

prevent a trap. Refer to the Installation Instructions for further details.

AUXILIARY "J" BOX

PLUG

COLLECTOR BOX TUBE

(PINK)

COLLECTOR BOX DRAIN TUBE

(BLUE)

COLLECTOR BOX TUBE

(GREEN)

CONDENSATE TRAP

INDUCER HOUSING DRAIN

TUBE (VIOLET)

COLLECTOR BOX EXTENSION TUBE

COLLECTOR BOX DRAIN

TUBE

(BLUE & WHITE STRIPED)

T

COLLECTOR BOX

EXTENSION DRAIN TUBE

DRAIN TUBE COUPLING

GAS VALVE

DRAIN TUBES ROUTED IN

FRONT OF GAS VALVE

CAP

BURNER ENCLOSURE PRESSU

REFERENCE TUBE ASSEMBL

A01052

Fig. 10 --

Furnace Pressure and Draining Tube Diagram

;;

;;

BURNER FLAME

BURNER

MANIFOLD

A89020

Fig. 11 --

Burner Flame

58MTB