4 installer settings – Braeburn 3220 Installer Guide User Manual
Page 9

INSTRUCTIONS
The Installer Settings must be properly configured in order for this thermostat to operate correctly. The Installer
Settings are menu driven. The portion of these settings that do not apply to your setup will be skipped. These
settings are indicated below with comments. More detail on each setting follows this table.
1. Press and hold down the
RETURN
and
buttons for 3 seconds.
2. Release both buttons and the first installer
setting will be displayed.
3. Change settings as required using the
or portion of the SpeedBar
®
.
4. Press
NEXT
or
BACK
to move to the next
or previous setting, press
RETURN
to exit.
No. Installer Setting
Factory
Setting
Comments
(
Notes follow this table)
Default
Options
(More information follows this table)
1 Temperature Scale
F DEG
F DEG
Select for Fahrenheit display
C DEG
Select for Celsius display
2 Auto Changeover
oF AUTO
oF AUTO
Disables Auto Changeover mode
ON AUTO
Enables Auto Changeover mode
11CONV
Select for 1H/1C Conventional system
22CONV
Select for 2H/2C Conventional system
3 System Type
11CONV
11HP
Select for 1H/1C Heat Pump system
22HP
Select for 2H/2C Heat Pump system
32HP
Select for 3H/2C Heat Pump system
1HD
Select for Heat Only Hydronic system
11HD
Select for Hydronic Heat/1C system
4 1st Stage Differential
0.5 DIF1
0.5, 1.0 or
Select a 1st stage temperature differential of .5°,
2.0 DIF1
1° or 2° F (0.2°, 0.5° or 1° C)
5 2nd Stage Differential
2.0 DIF2
1.0, 2.0, 3.0, Select a 2nd stage temperature differential of 1°,
[note 1]
4.0, 5.0 or 2°, 3°, 4°, 5° or 6° F (0.5°, 1°, 1.5°, 2°, 2.5° or 3° C)
6.0 DIF2
6 3rd Stage Differential
2.0 DIF3
1.0, 2.0, 3.0, Select a 3rd stage temperature differential of 1°, 2°,
[note 1]
4.0, 5.0 or 3°, 4°, 5° or 6° F (0.5°, 1°, 1.5°, 2°, 2.5° or 3° C)
6.0 DIF3
7 1st Stage Fan Control
HG FAN 1
HG FAN 1
Select for 1st stage Gas heating
[note 2]
HE FAN 1
Select for 1st stage Electric heating
8 Emergency Heat]
HE EMER
HE EMER
Select for Electric Emergency Heat
Fan Control
[note 3]
HG EMER
Select for Gas Emergency Heat
9 Reversing Valve
REVO
REVO
Select for cool active Reversing Valve (O terminal)
(O/B Terminal)
[note 4]
REVB
Select for heat active Reversing Valve (B terminal)
10 Fossil Fuel
AE AUX
AE AUX
Select for Electric Auxiliary heat (with compressor)
Backup Heat
[note 3]
AG AUX
Select for Gas Auxiliary heat (without compressor)
4 Installer Settings
9 Installer Guide
NOTE: Shaded areas below do not apply to the 3020.