Factory Setting

Switch

Default Options Comments

5

NOTES - Heat Pump Systems

[1] If batteries are installed the 24 Volt AC common connection is optional.
[2] Select O for cool active or B for heat active.
[3] Install a field supplied jumper between the W2 and E terminals if

there is no separate emergency heat relay installed.

Provide disconnect and overload protection as required.

CONV / HP CONV

F / C

F

HE / HG

HG

Set Installer Switches

4

CONV Select for conventional systems
HP

Select for heat pump systems

F

Select for fahrenheit temperature scale

C

Select for celsius temperature scale

HG

Select for gas heat

HE

Select for electric heat

Typical Wiring Configurations

NOTE: The “Installer Switch” option will be configured in the next step.

Heat Pump Systems

1 HEAT / 1 COOL - No Auxiliary Heat

Set Installer Switch to HP

Rh

24 Volt AC Power

Rc

Connected to Rh with supplied Jumper Wire

O or B Changeover Valve [note 2]
Y1

Compressor Relay

G

Fan Relay

C

24 Volt AC Transformer Common

[note 1]

2 HEAT / 1 COOL - Including Auxiliary Heat (2220 only)

Set Installer Switch to HP

Rh

24 Volt AC Power

Rc

Connected to Rh with supplied Jumper Wire

O or B Changeover Valve [note 2]
Y1

Compressor Relay (1st stage heating/cooling)

W2

Auxiliary Heat Relay (2nd stage heating)

[note 3]

E

Emergency Heat Relay

[note 3]

G

Fan Relay

C

24 Volt AC Transformer Common

[note1]

The Installer switches are located on the back of the thermostat and must
be properly set for this thermostat to operate properly.