Operation

The Premier 2-Zone Panel has LEDs to tell the installer and homeowner the current operating mode of the
panel. Refer to Figure 5 and the following descriptions of the panel LEDs for operation information.

Callout

LED

Description

1

Heartbeat

Flashes once per second when the panel is normal.

2

RH and RC

Lights when the HVAC equipment transformer(s) are receiving power.
Available only when C equipment terminal is wired.

3

24V Power

Lights when the panel is receiving power from the zoning transformer.

4

Damper

Lights red when the zone damper is closed, green when the zone
damper is open.

Notes:

• When no zones are calling, the panel will command all dampers to open.
• For maximum energy conservation, a 90 second purge will occur at the end of each call. No calls will

be answered until the purge is complete.

• Equipment staging is automatic based on time.
• No cooling calls will be answered if emergency heat is switched on.

9