Table 1: thermocouple output table, Figure 2: using the y99ab for the turn down test, Safety turn down test – BASO Pilot Burners User Manual
Page 3: Turn down test with the use of the y99ab test kit
Pilot Burners/Thermocouples Technical Bulletin 3
Table 1: Thermocouple Output Table
Thermocouple Lead
Series
Number
Code Number
Turn Down
(mV)
Open Circuit
Range (mV)
Minimum
Fixed Load
Voltage (mV)
K14
80
4
20 - 28
8
K15
88D, 88F, 88J, 88E,
88H
4
20 - 28
8
K16
87D, 87F, 87K, J87D,
K16K, L87D, N87D,
K16S, JC87F, L87F
4
25 - 35
8
K19
K19
4
25 - 35
8
!
WARNING:
Fire or Explosion Hazard. Avoid accumulation
of unburned gas and resulting personal injury or
property damage by making sure the main burner
lights under all pilot burner flame conditions that
maintain the BASO in the On position. Follow the
procedure below to assure the location of the pilot
with respect to the main burner is acceptable.
To perform the turn down test with the Y99AB Test Kit (purchasable
from your BASO Gas Products authorized wholesaler):
1. Disconnect the thermocouple from the BASO safety shutoff device
and connect it to the test kit (see Figure 2). Hold the BASO in the
open position during this test using battery power from the test kit.
Thermocouple
Lead
Reset
Button
Pilot Burner
Gas Line
Thermostat
y99ab
BASO
Power Unit
Manual
Pilot
Button
Manual
Main
Valve
44549-7
44549-8
Actuator
Red
Black
MILLIVOLTS
D.C.
PENN-BASO CONTROLS
0
10
20
30
40
50
10
0
300
500
700
900
MILLIAMPS
0-500
MILLIVOLTS
0-1000 0-50
ADJUST
MILLIVOLTS
MILLIAMPS
Power
Source
Figure 2: Using the Y99AB for the Turn Down Test
Safety
Turn Down Test
Turn Down Test
with the Use of
the Y99AB Test
Kit