Pilot Burners/Thermocouples Technical Bulletin 3

Table 1: Thermocouple Output Table

Thermocouple Lead

Series

Number

Code Number

Turn Down

(mV)

Open Circuit

Range (mV)

Minimum

Fixed Load

Voltage (mV)

K14

80

4

20 - 28

8

K15

88D, 88F, 88J, 88E,
88H

4

20 - 28

8

K16

87D, 87F, 87K, J87D,
K16K, L87D, N87D,
K16S, JC87F, L87F

4

25 - 35

8

K19

K19

4

25 - 35

8

!

WARNING:

Fire or Explosion Hazard. Avoid accumulation
of unburned gas and resulting personal injury or
property damage by making sure the main burner
lights under all pilot burner flame conditions that
maintain the BASO in the On position. Follow the
procedure below to assure the location of the pilot
with respect to the main burner is acceptable.

To perform the turn down test with the Y99AB Test Kit (purchasable
from your BASO Gas Products authorized wholesaler):

1. Disconnect the thermocouple from the BASO safety shutoff device

and connect it to the test kit (see Figure 2). Hold the BASO in the
open position during this test using battery power from the test kit.

Thermocouple

Lead

Reset

Button

Pilot Burner

Gas Line

Thermostat

y99ab

BASO

Power Unit

Manual

Pilot

Button

Manual

Main

Valve

44549-7

44549-8

Actuator

Red

Black

MILLIVOLTS

D.C.

PENN-BASO CONTROLS

0

10

20

30

40

50

10

0

300

500

700

900

MILLIAMPS

0-500

MILLIVOLTS

0-1000 0-50

ADJUST

MILLIVOLTS

MILLIAMPS

Power
Source

Figure 2: Using the Y99AB for the Turn Down Test

Safety
Turn Down Test

Turn Down Test
with the Use of
the Y99AB Test
Kit