12 VLV49A Series Universal Replacement Gas Valve Technical Bulletin
!
WARNING: Fire or Explosion Hazard. Avoid personal injury
or property damage by making sure the valve
functions properly and there are no gas leaks.
Follow this checkout procedure before leaving the
installation.
Make sure all components are functioning properly by performing the
following test:
1. Test for leaks on all pipe joints and connections upstream of the gas
valve with a soap solution.
2. Turn the thermostat to a low setting.
3. Turn on the gas and purge the gas lines of all air.
4. Turn the thermostat to a high setting. The appliance should operate in
accordance with the manufacturer’s specified sequence of operation.
5. Test for leaks on all pipe joints and connections downstream of the
gas valve with a soap solution.
6. Turn the thermostat down for at least 30 seconds and then back up
again. Verify successful ignition at least three times before leaving
the installation.
The VLV49A replacement valves are not field repairable. Do not
attempt field repairs. For a replacement valve, contact the nearest
BASO Gas Products distributor.