BASO H91 Series User Manual
Page 3

H91 Series BASOTROL Shutoff Gas Valve Installation Instructions 3
X indicates possible
locations for other controls.
Gas Flow
Shutoff Valve
H91
Gas Valve
X
X
Sediment
Trap
3 in. (76.2 mm)
Minimum
Burner
IN
OUT
Figure 3: Typical H91 Installation
Setup and Adjustments
Checkout
!
WARNING: Risk of Explosion or Fire.
Follow this or an equivalent checkout procedure 
after installation. Before leaving the installation, 
verify that the gas valve functions properly and that 
the system has no gas leaks. Gas leaks can lead to 
an explosion or fire, and may result in severe 
personal injury or death. 
Make sure all components are functioning properly by 
performing the following test. 
1.
Test all joints and connections for leaks with a 
rich soap and water solution. If leaks occur, see 
Step 8 in the Installation section. 
2.
Close the main manual shutoff valve and wait at 
least 5 minutes for unburned gas to escape from 
the appliance, and then reopen the shutoff valve. 
3.
Turn on the main electrical power switch and 
close the thermostat contacts. The appliance 
should operate in accordance with the 
manufacturer’s specified sequence of operation. 
4.
Turn the thermostat to a low dial setting to open 
the contacts. All burner flames should be 
extinguished. Repeat Steps 3 and 4 at least three 
times. 
5.
Return the thermostat to a normal setting before 
leaving the installation. 
Repairs and Replacement
!
CAUTION: Risk of Electric Shock.
Disconnect power supply before making electrical 
connections to avoid electric shock. 
!
WARNING: Risk of Explosion or Fire.
Shut off the gas supply at the main manual shutoff 
valve before installing or servicing the H91. Failure 
to shut off the gas supply can result in the release of 
gas during installation or servicing, which can lead to 
an explosion or fire, and may result in severe 
personal injury or death. 
!
WARNING: Risk of Explosion, Fire, or
Electric Shock. Label all wires before they are 
disconnected when replacing or servicing the H91. 
Wiring errors can cause improper or dangerous 
operation and may result in an explosion, fire, or 
electric shock leading to severe personal injury or 
death. 
Field repairs must not be made to the H91 valve. Any 
attempt to repair this assembly voids the 
manufacturer’s warranty. For a replacement valve, 
contact the original equipment manufacturer or the 
nearest BASO Gas Products distributor. 