Technical specifications – BASO G92 Series Automatic Pilot Gas Valve User Manual
Page 6

6 G92 Series BASOTROL Automatic Pilot Gas Valve Installation Instructions
Technical Specifications
Product
G92 Series BASOTROL Automatic Pilot Gas Valve
Maximum Operating
Pressure
0.5 psi (35 mbar)
Valve Body
Aluminum
Permissible Ambient
(Surface) Temperature
G92_ _ A and G92 _ _ C models without rotor valve 
 
CSA:
-30 to 175ºF (-34 to 79ºC)
UL:
-30 to 125ºF (-34 to 52ºC)
G92_ _ B models with rotor valve 
 
CSA:
32 to 175ºF (0 to 79ºC)
UL:
32 to 125ºF (0 to 52ºC)
Available Magnetic
Operator Cover Styles
Aluminum side conduit hub 
Aluminum top conduit hub 
Aluminum top without conduit hub 
Aluminum side outlet with eyelet 
Steel top conduit hub 
Plastic with 1/4 in. (6.35 mm) male quick-connect terminals 
Electrical Rating
25 VAC, 60 Hz, 0.3 ampere draw 
120 VAC, 60 Hz, 0.05 ampere draw 
240 VAC, 60 Hz, 0.03 ampere draw 
208/240 VAC, 60 Hz, 0.037 ampere draw (UL only) 
12 VDC, 0.5 ampere draw (CSA only) 
Recommended
Thermocouple Lead
Lengths
K15: 12 to 48 in. (305 to 1,220 mm) 
K16: 12 to 72 in. (305 to 1,830 mm) 
K19: 18 to 72 in. (457 to 1,830 mm) 
Wiring Connections
1/4 in. (6.35 mm) male quick-connect terminals or 
30 in. (762 mm) lead wires (other lengths are optional) 
Inlet Body Connection
1/2 in. NPT
Outlet Body Connection
1/2 or 3/4 in. NPT
Types of Gas
Natural, Liquefied Petroleum (LP), and LP gas-air mixtures
Packaging
Bulk pack supplied to original equipment manufacturer (individual pack optional)
Bulk Pack Quantity
32
Bulk Pack Weight
48 lb (22 kg)
Agency Listing
CSA Certificate Number 229521-1656050 (exclude G92CS_) 
UL File Number MH2926 (excludes G92CV_ and G92D_ _) 
Specification Standards
ANSI Z21.78, CSA 6.20 
UL Standard 372 and 429 
Performance specifications are nominal and conform to acceptable industry standards. All agency certification of BASO products is performed 
under dry and controlled indoor environmental conditions. Use of BASO products beyond these conditions is not recommended and may void 
the warranty. Product must be protected if exposed to water (dripping, spraying, rain, etc.) or other harsh environments. The original 
equipment manufacturer or end user is responsible for the correct application of BASO products. Consult BASO Gas Products LLC for 
questionable applications. BASO Gas Products LLC shall not be liable for damages or product malfunctions resulting from misapplication or 
misuse of its products. 
Refer to the G92 Series BASOTROL Automatic Pilot Gas Valve Product Bulletin (BASO-PB-G92) for necessary information on operating and 
performance specifications of this product. 
1007 South 12th Street 
PO Box 170 
Watertown, WI 53094 
www.baso.com
1-877-227-6427 (1-877-BASOGAS)
Published in U.S.A.
