This chapter of the User Guide provides information on error messages and
trouble-shooting 60 Series controllers. Some information in this chapter
refers to parameters that are not discussed in this guide. They are provided
as a quick reference to problems and solutions. Please refer to the technical
reference manual or consult your GSE distributor for additional information.

All 60 Series error messages are listed below in numerical order. The
leading two digits will appear on the numerical portion of the display, and
the message will appear on the two lines of dot matrix display. Following
each message is a summation of possible causes and probable remedy.

O

PERATIONAL

M

ODE

E

RROR

M

ESSAGES

02 UnderLoad!

Input signal less than negative full scale.
Check the load cell connections. If a 4-wire
load cell cable is being used, check that the
sense jumpers are in place. Verify that the
capacity selection P110 is correct. Use the
information parameters, especially P61100 to
check the setup and input signal.

03 Over-Load!

Input signal is greater than 104% of positive
full scale. Use same check as for underload.

04 # > Dsply

Number to be displayed will not fit within 6
digits. This will not normally occur for the
Gross, Net or Tare Weights but may result
while displaying the accumulated totals if the
amount exceeds 999,999. Clear the totals or
settle for only being able to transmit the totals.

05 Zero> Max.!

An attempt was made to zero out more than
allowed per P118 selection. Use the [TARE]
key for subtracting off container weights or if
large dead load is always to be present, apply
this dead load during the New Zero? prompt
during calibration to eliminate the offset.