Blue Sky UCM User Manual
Page 19
Installation and Operation Manual
18
PDU
ADDRESS
LOGICAL
REGISTER #
FUNCTION
CODES
DESCRIPTION
UNITS
SCALING
0x000D
14
3, 4
Total Charge Amp-Hours
AH
none
0x000E
15
3, 4
Upper byte of Lifetime Amp-Hours
AH
none
0x000F
16
3, 4
Lower 16 bits of Lifetime Amp-Hours
AH
none
0x0010
17
3, 4
Battery Temperature
ºC
Actual +60ºC.
(Range -60ºC to +80ºC)
0x0011
18
3, 4
Master: Heat Sink Temperature
ºC
Actual +60ºC
0x0012
19
3, 4
Master (Unit 0): Output Amps
A
X10
0x0013
20
3, 4
Master (Unit 0): Input Volts
V
X10
0x0014
21
3, 4
Master (Unit 0): Input Amps
A
X10
0x0015
22
3, 4
Unit 1: Heat Sink Temperature
ºC
none
0x0016
23
3, 4
Unit 1: Output Amps
A
X10
0x0017
24
3, 4
Unit 1: Input Volts
V
X10
0x0018
25
3, 4
Unit 1: Input Amps
A
X10
0x0019
26
3, 4
Unit 2: Heat Sink Temperature
ºC
none
0x001A
27
3, 4
Unit 2: Output Amps
A
X10
0x001B
28
3, 4
Unit 2: Input Volts
V
X10
0x001C
29
3, 4
Unit 2: Input Amps
A
X10
0x001D
30
3, 4
Unit 3: Heat Sink Temperature
ºC
none
0x001E
31
3, 4
Unit 3: Output Amps
A
X10
0x001F
32
3, 4
Unit 3: Input Volts
V
X10
0x0020
33
3, 4
Unit 3: Input Amps
A
X10
0x0021
34
3, 4
Unit 4: Heat Sink Temperature
ºC
none
0x0022
35
3, 4
Unit 4: Output Amps
A
X10
0x0023
36
3, 4
Unit 4: Input Volts
V
X10
0x0024
37
3, 4
Unit 4: Input Amps
A
X10
0x0025
38
3, 4
Unit 5: Heat Sink Temperature
ºC
none
0x0026
39
3, 4
Unit 5: Output Amps
A
X10
0x0027
40
3, 4
Unit 5: Input Volts
V
X10
0x0028
41
3, 4
Unit 5: Input Amps
A
X10
0x0029
42
3, 4
Unit 6: Heat Sink Temperature
ºC
none
0x002A
43
3, 4
Unit 6: Output Amps
A
X10
0x002B
44
3, 4
Unit 6: Input Volts
V
X10
0x002C
45
3, 4
Unit 6: Input Amps
A
X10
0x002D
46
3, 4
Unit 7: Heat Sink Temperature
ºC
none
0x002E
47
3, 4
Unit 7: Output Amps
A
X10
0x002F
48
3, 4
Unit 7: Input Volts
V
X10
0x0030
49
3, 4
Unit 7: Input Amps
A
X10
0x0031
50
3, 4, 6
Rated Battery AH Set Point
Amp-Hours none
0x0032
51
3, 4, 6
Charge Efficiency % Setpoint
%
none
0x0033
52
3, 4, 6
Self-Discharge % per month Setpoint
%
none
0x0034
53
3, 4, 6
Max. Battery Setpoint
V
X10
0x0035
54
3, 4, 6
<= Volts for Aux. Out Off Setpoint
V
X10
0x0036
55
3, 4, 6
>= Volts for Aux. Out On Setpoint
V
X10
0x0037
56
3, 4, 6
<= Amp-Hours for Aux. Out Off Setpoint
AH
none
0x0038
57
3, 4, 6
>= Amp-Hours for Aux. Out On Setpoint
AH
none
0x0039
58
3, 4, 6
Post Dusk Lights Setpoint
Hours
X10
0x003A
59
3, 4, 6
Pre-Dawn Lights Setpoint
Hours
X10
0x003B
60
3, 4, 6
Acceptance Charge Voltage Setpoint
V
X10
0x003C
61
3, 4, 6
Float Charge Voltage Setpoint
V
X10
0x003D
62
3, 4, 6
Equalize Charge Voltage Setpoint
V
X10
0x003E
63
3, 4, 6
Equalize Hours Setpoint
Hours
X10
0x003F
64
3, 4, 6
Auto Equalize Days Setpoint
Day
none
0x0040
65
3, 4, 6
Temperature Compensation Factor
mV/ºC/BatteryCell X
–100
0x0041
66
3, 4, 6
Float Transition Current Setpoint
Amps / 100 Amp-Hours X10
0x0042
67
3, 4, 6
Acceptance Hours Setpoint
Hours
X10
TABLE 5