Blue Sky UCM User Manual

Page 17

background image

Installation and Operation Manual

16

MODBUS OVER TCP

The UCM communicates on port 502. The Slave Address / Unit Identifier only applies if MODBUS/TCP communication is converted back to RS-485 by

an external user supplied TCP to RS-485 converter.

SLAVE ADDRESS / UNIT IDENTIFIER

DIP switches AD0 through AD7 as shown in Figure 4 set the UCM’s RS-485 RTU Slave Address / Unit Identifier within a selectable range of 1-247.

Factory default Slave Address / Unit Identifier is 1 (AD0 - AD7 all OFF).

¾

RTU address DIP switches AD0 through AD7 are only read when the UCM boots and subsequent changes with power

applied are ignored. Note: Booting the UCM with an address setting greater than 247 is not a valid address will restore all UCM
software settings to As Shipped Factory Defaults.

Actual RTU address setting = 1 + Sum of DIP’s weighting code set to ON

Examples: Address 1 = All Off , Address 5 = AD2 set to ON , Address 16 = AD0, 1, 2 & 3 set to ON

WEIGHTING CODE VALUE IF DIP = ON

AD0

AD1

AD2

AD3

AD4

AD5

AD6

AD7

1 2 4

8

16

32

64

128

ISOLATED RS-485

¾

WARNING: The RS-485 serial port is electrically isolated from battery negative to eliminate ground loops. Do not exceed ±100V

Peak difference between charge controller battery negative and MODBUS Master common. RS-485 terminal block COM connects
to circuit common on the user side of the isolation barrier. Both sides of the isolation barrier are powered by the UCM.


UCM DIP SWITCH AND JUMPER SETTINGS

FIGURE 4

RS-485 SERIAL COMMUNICATION SETTINGS

Default RS-485 serial communication settings are half duplex, 19.2k baud, 8 data bits, Even Parity and 1 stop bit. To access internal DIP switch selectors

and jumpers shown in Figure 4, remove the UCM cover.

RS-485 BAUD RATE AND PARITY SELECT

DIP SWITCH

FUNCTION

DESCRIPTION

BAUD0

Baud rate select

OFF = 19.2k baud, ON = 9600 baud

PARITY

Odd/Even Parity select

OFF = Even Parity, ON = Odd Parity

BAUD1

Parity Override

OFF = Parity per PARITY DIP switch, On = No Parity & 2 Stop Bits

TABLE 3

These connections for
factory use only. DO NOT
attach jumpers or other
connections.

Jumpers installed on these two jumper plugs configure
RS-485 for Half Duplex operation by connecting signals
A-to-A’ and B-to-B’. Factory default is jumpers installed.
Remove jumpers for Full Duplex operation.

MODBUS Isolated RS485 terminal block. COM
connected to user side of isolation barrier.

MODBUS
Address / Unit Identifier

Force use of TCP/IP
Comm defaults

MODBUS baud rate
& parity

)

DIP switch positions
are only read when
the UCM boots.
Changes following
boot are ignored.