Error Code

description

04

Discharge air sensor temperature is out of normal operating range. This can indicate an open

sensor, a short in the wiring, or a circuit board which is out of calibration. Take an ohm

reading across the sensor to ensure proper operation, check the wiring, and verify the value

in L035. Compare the sensor reading to the value in L112 to verify proper calibration of the

circuit board. Approximate ohm readings are 70° F = 1,199 ohms; 80° F = 941 ohms; 95° F

= 646 ohms.

05

Outdoor sensor (direct wired) temperature reading is out of normal operating range. The

sensor circuit may be open or shorted, or the processor control board may be out of calibra-

tion. Otherwise, verify that the outdoor sensor is connected to OS and SC on the 12-position

terminal block. Compare the sensor reading to the value in L113 to verify proper calibration

of the circuit board. Approximate ohm readings are 5° F = 7,646 ohms; 50° F = 2,024 ohms;

95° F = 646 ohms.

06

Outdoor temperature reading from the transmitting device (PLC system) is out of normal

operating range. Check the outdoor sensor attached to the transmitting device and the trans-

mitter for proper operation.

07

Main processor control board temperature sensor is out of normal operating range. Verify

that none of the clearances have been violated and inspect the condition of the processor con-

trol board.

08

External duct sensor temperature is out of normal operating range. This can indicate an open

sensor, a short in the wiring, or the relay driver board is out of calibration. Take an ohm

reading across the sensor to ensure proper operation, check the wiring, and verify the value

in L053. Compare the sensor reading to the value in L144 to verify proper calibration of the

circuit board. Approximate ohm readings are 60° F = 1552 ohms; 70° F = 1199 ohms; 80° F

= 941 ohms. Max 190°F, Min 0°

09

Auxiliary analog input is out of normal operating range. Currently not used.

10

Discharge air temperature has exceeded maximum standard operating temperatures.

11

Core C thermocouple temperature is out of normal operating range. An open, shorted, or

otherwise defective thermocouple or a circuit board which is out of calibration can cause

this. Check the thermocouple by taking a millivolt reading of the thermocouple. Compare the

thermocouple reading to the value in L136 to verify proper calibration of the circuit board.

Approximate DC mV readings are 200° F = 3.8 mV; 700° F = 15.2 mV; 1200° F = 27.0 mV.

Max. 1720°F, min 0°F

12

Core D thermocouple temperature is out of normal operating range. An open, shorted, or

otherwise defective thermocouple or a circuit board which is out of calibration can cause

this. Check the thermocouple by taking a millivolt reading of the thermocouple. Compare the

thermocouple reading to the value in L137 to verify proper calibration of the circuit board.

Approximate DC mV readings are 200° F = 3.8 mV; 700° F = 15.2 mV; 1200° F = 27.0 mV. .

Max. 1720°F, min 0°F

13

Core E thermocouple temperature is out of normal operating range. An open, shorted, or

otherwise defective thermocouple or a circuit board which is out of calibration can cause

this. Check the thermocouple by taking a millivolt reading of the thermocouple. Compare the

thermocouple reading to the value in L138 to verify proper calibration of the circuit board.

Approximate DC mV readings are 200° F = 3.8 mV; 700° F = 15.2 mV; 1200° F = 27.0 mV. .

Max. 1720°F, min 0°F

14

Core F thermocouple temperature is out of normal operating range. Not used in 9100 Series.

15

Core G thermocouple temperature is out of normal operating range. Not used in 9100 Series.

16

Core H thermocouple temperature is out of normal operating range. Not used in 9100 Series.